Technical Specification
Outputs
Conventional sounder circuits
Number of sounder circuits
Total sounder Load
Maximum Sounder Circuit Load
Sounder Circuit Fuses (F1/2/3/4)
End of line resistor
Fire Routing Equipment
Max Load
Fused (PTC2)
End of Line resistor
Fire Protecting Equipment
Max Load
Fused (PTC4)
End of Line resistor
Fault Routing equipment
Max Load
Fused (PTC1)
End of Line resistor
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load
Fuse (PTC5)
Auxiliary 24V Supply
Nominal Voltage
Fuse (PTC3)
Maximum current
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will effect the standby duration
RS485 Port (Mimic Repeater)
This is a serial output port for driving CF2000 Repeater panels, mimics etc..
This output is short circuit protected
Max Cable Length
Min Recommended cable size
Mechanical Specification
Weight including batteries
Weight excluding batteries
Dimensions (Standard batteries)
Type of Material (backbox)
Type of Material (Facia)
Flammability Rating
Total Number of knockouts
Diameter of Knock out
TERMINAL BLOCKS :
DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON THE TERMINAL BLOCK
: 4
: 1.0Amps (FH1204)
: 800mA
: 1.6 Amp (Quick Blow)
: 6k8
: 60 ma
: 100mA polyswitch
: 6k8
: 60 ma
: 100mA polyswitch
: 6k8
: 30 ma
: 100mA polyswitch
: 6k8
: 24 Volts 1 Amp
: 1.1 Amps polyswitch
: 24 Volts ±10%
: 300 mA Polyswitch
: 30 mA
: 2Km
: 1mm² (Screened)
: 10.6Kg
: 5.3Kg
: 400mm(L) x 320mm(H) x 170mm(D)
: Mild Steel (Power Coated)
: PC/ABS
: UL 94 V0
: 24
: 20mm