PC Comissioning Software

Device Input Programming
Fire
-> panel reports fire from device.
Fault
-> panel reports fault from device.
Reset
-> panel resets.
Silence
-> silence all currently active sounders.
Pre-Alarm
-> panel reports pre-alarm from device.
Non-Latching -> device won't latch in alarm condition, used in conjunction with isolates.
Optical-Heat -> mode changes between heat or optoheat mode
Heat
-> mode changes between Heat A1R and Heat CS
Isolate Zone / Address
user can define between zones or addresses to be isolated on activation of the device.
The isolate list button enables the user to enter upto 8 unique zones or addresses.
If non-latching has been enabled, Isolated devices can be un-isolated as the triggered device
returns to normal operation. (a call point keyswitch is an example for this application)