Door Contact (Dc) - ACT ACTpro Operating And Installation Instruction

120e single door station with 12v dc 2a power supply
Table of Contents

Advertisement

ACTpro 120e PSU Operating and Installation Manual
Push Button (PB)
Push button is connected between PB input and 0V. When
push button is pressed the main relay is activated for the
confi gured time.
Push button is also referred to as Exit Button, Egress Button,
Request To Exit.

Door Contact (DC)

Connect door contact between DC input and 0V.
Break Glass Monitoring only
The break glass monitoring features only
monitors the break glass status and does
not remove power from the lock. ACT
assumes a double pole break glass unit is
used, one pole to disrupt the power to the
lock the second pole for monitoring.
When the Break Glass is not activated the
B/GL input pin is held low at 0V. When the
Break Glass device is activated the B/GL
input pin will lose the 0V (goes high) and
report a Break Glass event. The lock should
be wired such that when the break glass is
activated power to the lock is removed.
9
Copyright © 2016 Access Control Technology Ltd. Part No.18-00100 Issue 1.0
DOOR CONTACT
MAGNETIC LOCK
EMERGENCY
DOOR RELEASE
NO C NC
BREAK GLASS
MONITORING
PUSH TO EXIT
NC C NO
Relay
0V
12V