5.8.1
SNMPv3 User Settings
The Liebert IntelliSlot-Unity card supports up to 20 SNMPv3 users. The top level page has a table
with settings for all 20. The page displays a link to edit the table columns displayed for each SNMPv3
user. The same settings may be accessed by clicking on a folder for a user, such as SNMPv3 User
Settings [1].
The Web page below shows the settings that can be changed for a SNMPv3 user. To display the
settings, click on any of the SNMPv3 Users Setting links. After making any changes, click Save to
make the changes effective; click Cancel to discard the changes.
SNMPv3 User Settings
• SNMPv3 User Enable—Select to enable read, write or sending notifications with the user's
credentials.
• SNMPv3 Username—The User name the authentication and privacy settings apply to. This
string can be composed of printable characters except colon, tab, double quote, and question mark.
• SNMPv3 Access Type—Read Only, Read/Write or Traps only
• SNMPv3 Authentication—Cryptographic algorithm used for authentication: None, MD5 or
SHA-1
• SNMPv3 Authentication Secret—Pass phrase or password used for SNMPv3 Get request. This
string can be composed of printable characters with the exception of colon, tab, double quote, and
question mark. Note: The entry must be 8 or more characters but not more than 64.
• SNMPv3 Privacy—Cryptographic algorithm used for encryption: None or DES.
• SNMPv3 Privacy Secret—Pass phrase or password used for SNMPv3 Get request. This string can
be composed of printable characters with the exception of colon, tab, double quote, and question
mark. Note: The entry must be 8 or more characters but not more than 64.
• SNMPv3 Trap Target Addresses—Network hosts that will receive SNMPv3 traps, identified with
either a network name or IP address. Multiple addresses must be separated by commas. The field
has a maximum length of 125 characters
• SNMPv3 Trap Port—Port used by the target host for receiving SNMPv3 traps; default is 162.
®
®
Liebert
IntelliSlot
Unity
™
Card
Edit the Liebert IntelliSlot Unity Card Configuration
Click on a SNMPv3User
Settings folder or a link
to get this settings page.