Enable Bacnet Protocol; Figure 7 Modbus-Rs-485 - Emerson Liebert IntelliSlot Unity-DP User Manual

Web, snmp, modbus, bacnet, ydn23
Table of Contents

Advertisement

Figure 7
Modbus-RS-485
3.1.2

Enable BACnet Protocol

Contact your system administrator or building management system administrator if you are
uncertain about the settings.
1. Select Unity Tab > Protocols > BACnet.
2. Click on Edit and enter a user name and password if required.
3. Enter the Managed Device Write Access level (Read Only or Read/Write). This determines a
user's ability to change settings in the Liebert IntelliSlot Unity card.
4. Choose the BACnet interface, either BACnet IP or BACnet MSTP
5. Set the Device Object Instance Number.
6. Set the Device Object Name.
7. Set the APDU Timeout.
8. Set the APDU Retries.
9. Click Save to confirm the changes or click on Cancel to discard them.
10. Configure the BACnet interface chosen; refer to Configure BACnet IP Protocol or Configure
BACnet MSTP Protocol. For additional details, see 5.6 - Protocols Folder—BACnet Folder.
13
Enable Communication Protocols
Node ID must
be unique on
the RS-485 bus
this card is
connected to.
®
®
Liebert
IntelliSlot
Unity
Card