SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR

SR3 GOOSE configuration - Lab

4–22
GGIO5 contains the status of the remote inputs received by this relay while GGIO1 contains
the status of the remote outputs configured under Setpoints > S1 Relay Setup >
Communication > Transmission.
This section will explain how to setup GOOSE messaging between two relays using the SR3
IEC61850 Device Configurator. Please note that only settings files of relay's with firmware
version 1.41 or higher, with the 3E option, support this feature.
For simplicity, the objective of this exercise will be to demonstrate how to configure the
SR3 relay labeled 228 (using the SR3 IEC61850 Device Configurator portion of the SR3
software) to send a GOOSE message containing the status of Virtual Input 1 to the SR3
relay labeled 254.
Once the IP address and subnet mask have been configured within each relay using the
procedures outlined earlier in this guide, and the power to the relays cycled, the relays are
ready to be connect though a switch to the computer running the SR3 configuration
software. Please note that an IP address and subnet mask are not required for GOOSE
messaging but are required to allow configuration of the relays via Ethernet.
CHAPTER 4: SR3 IEC61850 GOOSE
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE