CHAPTER 3: ETHERNET INTERFACE
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
DNP 3.0 Device Profile
□ Configurable
Requires Application Layer Confirmation:
□ Never
□ Always
⊠ When reporting Event Data
⊠ When sending multi-fragment responses
□ Sometimes
□ Configurable
Timeouts while waiting for:
Data Link Confirm:
Complete Appl. Fragment:
Application Confirm:
Complete Appl. Response:
Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Counter change scanning period: 500 ms
Frozen counter event scanning period: 500 ms
Sends/Executes Control Operations:
WRITE Binary Outputs
SELECT/OPERATE
DIRECT OPERATE
DIRECT OPERATE – NO ACK
Count > 1
Pulse On
Pulse Off
Latch On
Latch Off
Queue
Clear Queue
Explanation of 'Sometimes': Object 12 points are mapped to Virtual Inputs and Commands (Force
Coils). Both "Pulse On" and "Latch On" operations perform the same function in the 350 ; that is, the
appropriate Virtual Input or Coil is put into the "On" state. The On/Off times and Count value are
ignored. "Pulse Off" and "Latch Off" operations put the appropriate Virtual Input or Coil into the "Off"
state. "Trip" and "Close" operations both put the appropriate Virtual Input or coil into the "On" state if
a paired mapping is set, otherwise "Trip" will put into "Off" and "Close" will put into "On".
Reports Binary Input Change Events when no
specific variation requested:
□ Never
⊠ Only time-tagged
□ Only non-time-tagged
□ Configurable
Sends Unsolicited Responses:
□ Never
□ Configurable
DNP ETHERNET PROTOCOL SETTINGS
⊠ None
□ Fixed
⊠ None
□ Fixed
□ None
⊠ Fixed at 10 s □ Variable □ Configurable
⊠ None □ Fixed at ___ □ Variable □ Configurable
⊠ Never □ Always
□ Sometimes □Configurable
□ Never
⊠ Always
□ Sometimes □ Configurable
□ Never
⊠Always
□ Sometimes □ Configurable
□ Never
⊠ Always
□ Sometimes □ Configurable
⊠ Never
□ Always
□ Sometimes □ Configurable
□ Never
□ Always
⊠ Sometimes □ Configurable
□ Never
□ Always
⊠ Sometimes
□ Never
□ Always
⊠ Sometimes
□ Never
□ Always
⊠ Sometimes
⊠ Never
□ Always □ Sometimes
⊠ Never
□ Always □ Sometimes
Reports time-tagged Binary Input Change
Events when no specific variation
requested:
□ Never
⊠ Binary Input Change With Time
□ Binary Input Change With Relative Time
□ Configurable (attach explanation)
Sends Static Data in Unsolicited Responses:
⊠ Never
□ When Device Restarts
□ Variable □ Configurable
□ Variable
□ Configurable
□ Configurable
□ Configurable
□ Configurable
□ Configurable
□ Configurable
3–17