Link Layer; Application Layer - GE 350 Communications Manual

Feeder protection and control
Hide thumbs Also See for 350:
Table of Contents

Advertisement

IEC 60870-5-103 SERIAL COMMUNICATION

Link layer

Application layer

2–16
Optical interface
Glass fibre
Plastic fibre
F-SMA type connector
BFOC/2,5 type connector
Transmission speed
There are no choices for the Link Layer.
Transmission mode for application data
Mode 1 (least significant octet first), is used exclusively in this companion standard.
Common address of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor direction
Table 2-4: System functions in monitor direction
INF
<0>
<0>
<2>
<3>
<4>
<5>
Table 2-5: Status indications in monitor direction
INF
Semantics
<16>
Auto-recloser active
<17>
Teleprotection active
<18>
Protection active
<19>
LED reset
<20>
Monitor direction blocked
<21>
Test mode
<22>
Local parameter setting
<23>
Characteristic 1
<24>
Characteristic 2
<25>
Characteristic 3
<26>
Characteristic 4
<27>
Auxiliary input 1
CHAPTER 2: RS485 INTERFACE
9600 bits/s
19200 bits/s
Semantics
End of general interrogation
Time synchronization
Reset FCB
Reset CU
Start/restart
Power on
350 Identifier
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
350 Data Text