CHAPTER 4: SR3 IEC61850 GOOSE
350 FEEDER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
SR3 GOOSE CONFIGURATION VIA THE IEC 61850 CONFIGURATOR
2.4.
Within the GOOSE transmission control block work area you will see the SR3xx
IED icon with IED name "one". Click on the icon and open the directory tree until
the GOOSE ID is displayed.
2.5.
Click on the GOOSE ID to allow the GOOSE transmission properties work area to
become visible for editing.
2.6.
Enter a unique name for the GOOSE transmission. In our example we will use
the name TX1. Once entered, and the configuration complete, the name TX1
will be assigned to the GOOSE message transmitted from this relay. Optionally,
you can also enter a unique name for the GOOSE control block.
2.7.
The directory tree within the data set source work area can be expanded such
that digital and analog data values of different logical nodes can be accessed.
Sixty four of these data values can be dragged into the data settlements work
area to form the GOOSE message that will be transmitted.