Rosemount 5900 Series
Figure 3-23. Rosemount 5900
wiring diagram for 2-in-1 version
with two tankbuses
TankMaster PC
Power supply
3-48
Preliminary
The Rosemount 5900 2-in-1 version
The 2-in-1 version of the Rosemount 5900 has two separate level gauges
placed in the same housing. One of the tankbuses can be terminated.
The 2-in-1 version can be connected to two separate tankbuses as illustrated
in Figure 3-23 and 3-24, or to a single tankbus as illustrated in Figure 3-25 on
page 3-50.
Terminal X1 is an intrinsically safe tankbus input for level gauge 1, and
terminal X4 connects to the second level gauge.
Figure 3-23 illustrates a wiring diagram with a 2-in-1 version of the
Rosemount 5900 level gauge which is "daisy-chained" to a Rosemount 2240
multi-input temperature transmitter. Note that the Primary Tankbus is
terminated in the 5900 terminal block (X2).
Rosemount 2410 Tank Hub
See also "Terminal Blocks" on page 3-44 for information on terminal block
connections.
375 Field Communicator
ROSEMOUNT 5900 RADAR
LEVEL GAUGE (2-IN-1)
Termination
Rosemount 2240
multi-input temperature
transmitter
Primary Tankbus
(gauge 1)
Reference Manual
300520EN, Rev AA
November 2009
Secondary Tankbus
(gauge 2)