IMPORTANT:
Check for indicts before and after each firmware update.
FRU
Blade – Requires a nPar outage
XFM — Requires a Complex outage
Process
1. Power OFF the partition the blade is assigned to. (See
Note below this table)
2. Remove/Replace the suspect blade following the
instructions in the service guide.
3. Use the update firmware <uri> all command,
pointing it to the <uri> of a bundle file that matches what is
currently installed on the complex. This command check
the current firmware version of all installed FRUs and will
only update FRUs that do not match the complex firmware
version.
4. Check for indicts.
5. Power on the partition.
1. Power OFF all partitions.
2. Remove and replace the suspect XFM following the
instructions in the service guide.
IMPORTANT:
Do not mix XFM and XFM2 crossbar modules in the
same system.
3. Use the update firmware <uri> all command,
pointing it to the <uri> of a bundle file that matches what is
currently installed on the complex. This command check
the current firmware version of all installed FRUs and will
only update FRUs that do not match the complex firmware
version.
4. Check for indicts.
5. Power on all partitions.