Check either Yes or No. If No, include comment or date.
Computer Room
Number
Area or condition
5.
Is a raised floor installed and in good condition?
What is the floor to ceiling height? [228 cm (7.5 ft)
minimum]
6.
Is the raised floor adequate for equipment loading?
7.
Are channels or cutouts available for cable routing?
8.
Is a network line available?
9.
Is a telephone line available?
10.
Are customer-supplied peripheral cables and LAN cables
available and of the proper type?
11.
Are floor tiles in good condition and properly braced?
12.
Is floor tile underside shiny or painted?
If painted, judge the need for particulate test.
Power and Lighting
13.
Are lighting levels adequate for maintenance?
14.
Are AC outlets available for servicing needs (for example,
laptop usage)?
15.
Does the input voltage correspond to equipment
specifications?
15a.
Is dual source power used? If so, identify types and
evaluate grounding.
16.
Does the input frequency correspond to equipment
specifications?
17.
Are lightning arrestors installed inside the building?
18.
Is power conditioning equipment installed?
19.
Is a dedicated branch circuit available for equipment?
20.
Is the dedicated branch circuit less than 22.86 m (75 ft)?
Yes
No
Comment or
Date
Table Continued