Using the OBELISK top2 memory card
L The OBELISK top2 memory card is not included in the
scope of supply of the device, but can be ordered as an
accessory (9070404).
All functions can also be set on the PC using the OBELISK
software and transferred to the device via the memory card.
Insert memory card in the time switch
¾
Read in/out saved switching times and device setups in
¾
the time switch or start Obelisk program
Remove memory card after copying etc.
¾
!
Avoid mechanical overload and contamination during
storage/transport
Copying OBELISK → Time switch
This copies the switch programme and optionally all time
switch settings (e.g. form time etc.) from the memory card to
the time switch.
Copying Time switch → OBELISK
Copies all switch programmes and settings from the
time switch to the memory card.
Starting OBELISK program
Takes over the switching times that are programmed on the
memory card.
As soon as the memory card is removed, the switching times
of the time switch are re-activated.
OBELISK
u
COPY
COPY TIME
OBELISK ->
SWITCH ->
TIME
OBELISK
OVERWRITE
OVERWRITE
OK
OK
L The current OBELISK top2 PC software is available at
www.theben.de.

Resetting the time switch

Press the 4 buttons simultaneously
¾
▻ You can choose between RETAIN PROGRAMS and
DELETE PROGRAMS
u
u
RUN OBELISK
CHECK
OBELISK

6. Technical data

Operating voltage
Standby
Switching capacity max.
Switching capacity
Switching capacity min.
Protection rating
Protection class
Protection class
Operating temperature
Shortest switching time
Power reserve
Time accuracy (typical)
Rated impulse voltage
Pollution degree
Contact
Max. switching cycles with 16 A
resistive load
Incandescent lamp load
Halogen lamp load (230 V)
Fluorescent lamps (LLB low-loss
ballasts):
uncompensated (230 V)
series compensated (230 V)
parallel compensated (230 V)
Fluorescent lamps (EB – Electronic
Ballasts) (230 V)
Compact fluorescent lamps (EB)
LED lamps (< 2 W)
LED lamps (2 W – 8 W)
LED lamps (> 8 W)
Corresponds to type 1 BSTU in
accordance with IEC/EN 60730-2-7
or IEC/EN 60730-1
Switching of any external conductor
is permitted.
Approved for switching SELV and
mains voltage
7. Contact
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Phone +49 7474 692-0
Fax +49 7474 692-150
Hotline
Phone +49 7474 692-369
hotline@theben.de
Addresses, telephone numbers etc.
www.theben.de
12–24 V, 50–60 Hz, +10 % / –15 %,
12–24 V DC, +10 % / –15 %
0.9 W (1714100)
0.2 W (1724100)
16 A (at 250 V AC, cos ϕ = 1)
2 A (at 250 V AC, cos ϕ = 0.6)
10 mA/230 V AC
100 mA/12 V AC/DC
IP 20 in accordance with EN 60529
Protection class: II in accordance
with EN 60730-1 subject to correct
installation for supply with FELV and/
or mains switching
III for supply with SELV and switching
of SELV
–30 °C ... +55 °C
1 min.
10 years at +20 °C
± 0.25 s/day (25 °C)
4 kV
2
Changeover contact, µ contact
50 000
1000 W
1000 W
1000 VA
1000 VA
80 W (max. 12 µF)
120 W
30 W
6 W
20 W
25 W
7