30-Amp, 50 Or 60 Hz, Three-Phase Dkc; 50-Amp, 50 Or 60 Hz, Single-Phase Dku - HP StorageWorks XP12000 Site Prep Manual

Hide thumbs Also See for StorageWorks XP12000:
Table of Contents

Advertisement

30-amp, 50 or 60 Hz, three-phase DKC

Parameter
Minimum operating voltage
(VAC)
Maximum operating voltage
(VAC)
Rated line current per power
cord (amps RMS)
Number of power cords
Recommended circuit breakers
(amps)
Number of circuit breakers
Dropout carry-through time at
minimum line voltage (ms)

50-amp, 50 or 60 Hz, single-phase DKU

Parameter
Minimum operating voltage
(VAC)
Maximum operating voltage
(VAC)
Rated line current per power
cord (amps RMS)
Number of power cords
Recommended circuit breakers
(amps)
Number of circuit breakers
Dropout carry-through time at
minimum line voltage (ms)
62
Electrical specifications
200
208
220
230
VAC
VAC
VAC
VAC
184
191
202
212
212
220
233
244
13
12.5
11.9
11.3 10.9
2
2
2
30
30
30
30
2
2
2
60
60
60
60
200
208
VAC
VAC
184
191
212
220
18
17.3
2
2
50
50
2
2
60
60
240
380
400
VAC
VAC
VAC
221
350
368
254
403
424
6.9
6.5
2
2
2
2
30
30
30
2
2
2
2
60
60
60
220
230
VAC
VAC
202
212
233
244
16.4
15.7
2
2
50
50
2
2
60
60
415
VAC
382
440
6.3
2
30
2
60
240
VAC
221
254
15.0
2
50
2
60