Settings - Siemens SIPROTEC 7SK80 Manual

Motor protection
Hide thumbs Also See for SIPROTEC 7SK80:
Table of Contents

Advertisement

Functions
2.1 General
In address 192 Cap. Volt.Meas. you can specify whether you want to employ capacitive voltage measure-
ment. When selecting YES, you have to specify the bushing capacitance, the line and stray capacitance for the
capacitive voltage dividers at the voltage inputs in addresses 241 to 246 (see 2.1.3.2).
With capacitive voltage measurement several functions are not available or only partly. See table 2-1 in section
2.1.3.2 for more information regarding this topic.
In address 617 ServiProt (CM) you can specify for which purpose port B is used. T103 means that the
device is connected to a control and protection facility via serial port, DIGSI means that you are using the port
to connect DIGSI and RTD-RS485 means that you are using the port to connect an RTD box. Disabled indi-
cates that you can not use port B.
The flexible protection functions can be configured via parameter FLEXIBLE FUNC.. You can create up to 20
flexible functions by setting a checkmark in front of the desired function (an example is given in the section
2.14). If the checkmark of a function is removed, all settings and configurations made previously will be lost.
After re-selecting the function, all settings and configurations are in default setting. Setting of the flexible func-
tion is done in DIGSI under „Settings", „Additional Functions" and „Settings". The configuration is done, as
usual, under „Settings" and „Masking I/O (Configuration Matrix)".

2.1.1.3 Settings

Addr.
Parameter
103
Grp Chge OPTION
104
OSC. FAULT REC.
112
Charac. Phase
113
Charac. Ground
116
67N/67N-TOC
117
Coldload Pickup
122
InrushRestraint
130
S.Gnd.F.Dir.Ch
131
Sens. Gnd Fault
140
46
141
48
30
Setting Options
Disabled
Enabled
Disabled
Enabled
Disabled
Definite Time
TOC IEC
TOC ANSI
Disabled
Definite Time
TOC IEC
TOC ANSI
Disabled
Definite Time
TOC IEC
TOC ANSI
Disabled
Enabled
Disabled
Enabled
cos ϕ / sin ϕ
V0/I0 ϕ mea.
Disabled
Definite Time
User Defined PU
Disabled
TOC ANSI
TOC IEC
Definite Time
Disabled
Enabled
Default Setting
Disabled
Setting Group Change Option
Enabled
Oscillographic Fault Records
Definite Time
50/51
Definite Time
50N/51N
Definite Time
67N, 67N-TOC
Disabled
Cold Load Pickup
Disabled
2nd Harmonic Inrush Restraint
cos ϕ / sin ϕ
(sens.) Ground fault dir. character-
istic
Disabled
(sensitive) Ground fault
Disabled
46 Negative Sequence Protection
Enabled
48 Startup Time Supervision for
Motors
E50417-G1140-C344-A4, Release date 08.2010
Comments
SIPROTEC, 7SK80, Manual