2.7 Motor Protection (Motor Starting Protection 48, Motor Restart Inhibit 66, Load Jam Protection)
Addr.
Parameter
4302
IStart/IMOTnom
4303
T START MAX
4304
T Equal
4305
I MOTOR NOMINAL
4306
MAX.WARM STARTS
4307
#COLD-#WARM
4308
Kτ at STOP
4309
Kτ at RUNNING
4310
T MIN. INHIBIT
4311
ROTOR OVERLOAD
4401
Load Jam Prot.
4402
Load Jam I>
4403
TRIP DELAY
4404
I Alarm
4405
ALARM DELAY
4406
T Start Blk.
140
C
Setting Options
1.10 .. 10.00
1 .. 320 sec
0.0 .. 320.0 min
1A
0.20 .. 1.20 A
5A
1.00 .. 6.00 A
1 .. 4
1 .. 2
0.2 .. 100.0
0.2 .. 100.0
0.2 .. 120.0 min
ON
OFF
Alarm Only
OFF
ON
Alarm Only
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
0.00 .. 600.00 sec
1A
0.50 .. 12.00 A
5A
2.50 .. 60.00 A
0.00 .. 600.00 sec
0.00 .. 600.00 sec
Default Setting
4.90
I Start / I Motor nominal
10 sec
Maximum Permissible
Starting Time
1.0 min
Temperature Equalizaton
Time
1.00 A
Rated Motor Current
5.00 A
2
Maximum Number of
Warm Starts
1
Number of Cold Starts -
Warm Starts
5.0
Extension of Time Con-
stant at Stop
2.0
Extension of Time Con-
stant at Running
6.0 min
Minimum Restart Inhibit
Time
ON
Rotor Overload Protection
OFF
Load Jam Protection
2.00 A
Load Jam Tripping
Threshold
10.00 A
1.00 sec
Load Jam Trip Delay
1.80 A
Load Jam Alarm Thresh-
old
9.00 A
1.00 sec
Load Jam Alarm Delay
10.00 sec
Load Jam Blocking after
motor start
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010