Addr.
Parameter
9052A
RTD 5 LOCATION
9053
RTD 5 STAGE 1
9054
RTD 5 STAGE 1
9055
RTD 5 STAGE 2
9056
RTD 5 STAGE 2
9061A
RTD 6 TYPE
9062A
RTD 6 LOCATION
9063
RTD 6 STAGE 1
9064
RTD 6 STAGE 1
9065
RTD 6 STAGE 2
9066
RTD 6 STAGE 2
9071A
RTD 7 TYPE
9072A
RTD 7 LOCATION
9073
RTD 7 STAGE 1
9074
RTD 7 STAGE 1
9075
RTD 7 STAGE 2
9076
RTD 7 STAGE 2
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Setting Options
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
2.15 Temperature Detection via RTD Boxes
Default Setting
Other
RTD 5: Location
100 °C
RTD 5: Temperature Stage 1
Pickup
212 °F
RTD 5: Temperature Stage 1
Pickup
120 °C
RTD 5: Temperature Stage 2
Pickup
248 °F
RTD 5: Temperature Stage 2
Pickup
Not connected
RTD 6: Type
Other
RTD 6: Location
100 °C
RTD 6: Temperature Stage 1
Pickup
212 °F
RTD 6: Temperature Stage 1
Pickup
120 °C
RTD 6: Temperature Stage 2
Pickup
248 °F
RTD 6: Temperature Stage 2
Pickup
Not connected
RTD 7: Type
Other
RTD 7: Location
100 °C
RTD 7: Temperature Stage 1
Pickup
212 °F
RTD 7: Temperature Stage 1
Pickup
120 °C
RTD 7: Temperature Stage 2
Pickup
248 °F
RTD 7: Temperature Stage 2
Pickup