Siemens SIPROTEC 7SK80 Manual page 448

Motor protection
Hide thumbs Also See for SIPROTEC 7SK80:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
9051A
RTD 5 TYPE
9052A
RTD 5 LOCATION
9053
RTD 5 STAGE 1
9054
RTD 5 STAGE 1
9055
RTD 5 STAGE 2
9056
RTD 5 STAGE 2
9061A
RTD 6 TYPE
9062A
RTD 6 LOCATION
9063
RTD 6 STAGE 1
9064
RTD 6 STAGE 1
9065
RTD 6 STAGE 2
9066
RTD 6 STAGE 2
9071A
RTD 7 TYPE
9072A
RTD 7 LOCATION
9073
RTD 7 STAGE 1
9074
RTD 7 STAGE 1
9075
RTD 7 STAGE 2
9076
RTD 7 STAGE 2
9081A
RTD 8 TYPE
9082A
RTD 8 LOCATION
9083
RTD 8 STAGE 1
9084
RTD 8 STAGE 1
9085
RTD 8 STAGE 2
9086
RTD 8 STAGE 2
448
Function
C
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
RTD-Box
Oil
Ambient
Winding
Bearing
Other
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
RTD-Box
-50 .. 250 °C; ∞
RTD-Box
-58 .. 482 °F; ∞
Setting Options
Default Setting
Not connected
Other
100 °C
212 °F
120 °C
248 °F
Not connected
Other
100 °C
212 °F
120 °C
248 °F
Not connected
Other
100 °C
212 °F
120 °C
248 °F
Not connected
Other
100 °C
212 °F
120 °C
248 °F
E50417-G1140-C344-A4, Release date 08.2010
Comments
RTD 5: Type
RTD 5: Location
RTD 5: Temperature Stage 1
Pickup
RTD 5: Temperature Stage 1
Pickup
RTD 5: Temperature Stage 2
Pickup
RTD 5: Temperature Stage 2
Pickup
RTD 6: Type
RTD 6: Location
RTD 6: Temperature Stage 1
Pickup
RTD 6: Temperature Stage 1
Pickup
RTD 6: Temperature Stage 2
Pickup
RTD 6: Temperature Stage 2
Pickup
RTD 7: Type
RTD 7: Location
RTD 7: Temperature Stage 1
Pickup
RTD 7: Temperature Stage 1
Pickup
RTD 7: Temperature Stage 2
Pickup
RTD 7: Temperature Stage 2
Pickup
RTD 8: Type
RTD 8: Location
RTD 8: Temperature Stage 1
Pickup
RTD 8: Temperature Stage 1
Pickup
RTD 8: Temperature Stage 2
Pickup
RTD 8: Temperature Stage 2
Pickup
SIPROTEC, 7SK80, Manual

Advertisement

Table of Contents
loading

Table of Contents