Settings - Siemens SIPROTEC 7SK80 Manual

Motor protection
Hide thumbs Also See for SIPROTEC 7SK80:
Table of Contents

Advertisement

2.15.3

Settings

Addresses which have an appended "A" can only be changed with DIGSI, under "Display Additional Settings".
Addr.
Parameter
9000
UDP Port
9001
IP address[0]
9002
IP address[1]
9003
IP address[2]
9004
IP address[3]
9005
UDP Port
9006
IP address[0]
9007
IP address[1]
9008
IP address[2]
9009
IP address[3]
9011A
RTD 1 TYPE
9012A
RTD 1 LOCATION
9013
RTD 1 STAGE 1
9014
RTD 1 STAGE 1
9015
RTD 1 STAGE 2
9016
RTD 1 STAGE 2
9021A
RTD 2 TYPE
9022A
RTD 2 LOCATION
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
Setting Options
0 .. 65535
0 .. 255
0 .. 255
0 .. 255
0 .. 255
0 .. 65535
0 .. 255
0 .. 255
0 .. 255
0 .. 255
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
-50 .. 250 °C; ∞
-58 .. 482 °F; ∞
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Oil
Ambient
Winding
Bearing
Other
2.15 Temperature Detection via RTD Boxes
Default Setting
5000
UDP service port in the RTD box
0
IP address[0] of RTD box,
connec. by UDP
0
IP address[1] of RTD box,
connec. by UDP
0
IP address[2] of RTD box,
connec. by UDP
0
IP address[3] of RTD box,
connec. by UDP
5000
UDP service port in the RTD box
0
IP address[0] of RTD box,
connec. by UDP
0
IP address[1] of RTD box,
connec. by UDP
0
IP address[2] of RTD box,
connec. by UDP
0
IP address[3] of RTD box,
connec. by UDP
Pt 100 Ω
RTD 1: Type
Oil
RTD 1: Location
100 °C
RTD 1: Temperature Stage 1
Pickup
212 °F
RTD 1: Temperature Stage 1
Pickup
120 °C
RTD 1: Temperature Stage 2
Pickup
248 °F
RTD 1: Temperature Stage 2
Pickup
Not connected
RTD 2: Type
Other
RTD 2: Location
Functions