DESCRIPTION
The Models SR631/SR632 (Catalog #2113.47 and #2114.79) are designed for use in industrial
environments. The ergonomic design allows them to easily attach to cables or small bus bars. The
"circular" jaws guarantee a very good accuracy and low phase shift. The probes have a measurement
range up to 1000Arms. continuous and are compatible with any AC ammeter, multimeter, or other current
measurement instrument with an input impedance lower than 0.6. To achieve the stated accuracy, use
the SR631/SR632 with an ammeter having an accuracy of 0.75% or better.
WARNING
The safety warnings are provided to ensure the safety of personnel and proper operation of the
instrument. Read the instruction completely.
• Use caution on any circuit: potentially high voltages and currents may be present and may pose a
shock hazard.
• Do not use the probe if damaged. Always connect the current probe to the measuring device
before it is connected around the conductor
• Do not use on non-insulated conductor with a potential to ground greater than 600V CAT III
pollution 2. Use extreme caution when clamping around bare conductors or bus bars.
• Before each use, inspect the probe; look for cracks in housing or output cable insulation.
• Do not use clamp in wet environment or in locations that hazardous gases exist.
• Do not use the probe anywhere beyond the tactile barrier.
INTERNATIONAL ELECTRICAL SYMBOLS
This symbol signifies that the current probe is protected by double or reinforced insulation. Use
only factory specified replacement parts when servicing the instrument.
This symbol signifies CAUTION! and requests that the user refer to the user manual before using
the instrument.
This is a type A current sensor. This symbol signifies that application around and removal from
HAZARDOUS LIVE conductors is permitted.
DEFINITION OF MEASUREMENT CATEGORIES
CAT I: For measurements on circuits not directly connected to the AC supply wall outlet such as protected
secondaries, signal level, and limited energy circuits.
CAT II: For measurements performed on circuits directly connected to the electrical distribution system.
Examples are measurements on household appliances or portable tools.
CAT III: For measurements performed in the building installation at the distribution level such as on
hardwired equipment in fixed installation and circuit breakers.
CAT IV: For measurements performed at the primary electrical supply (<1000V) such as on primary
overcurrent protection devices, ripple control units, or meters.
RECEIVING YOUR SHIPMENT
Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify your
distributor of any missing items. If the equipment appears to be damaged, file a claim immediately with the
carrier and notify your distributor at once, giving a detailed description of any damage.

Advertisement

loading

Summary of Contents for AEMC SR631

  • Page 1 User Manual DESCRIPTION The Models SR631/SR632 (Catalog #2113.47 and #2114.79) are designed for use in industrial environments. The ergonomic design allows them to easily attach to cables or small bus bars. The “circular” jaws guarantee a very good accuracy and low phase shift. The probes have a measurement range up to 1000Arms.
  • Page 2: Electrical Specifications

    Barrier (keep hands below this barrier) 1.38" (35 mm) 1.77" 1.71" (45 mm) (43.5 mm) 3.90" (99 mm) SR631 SR632 ELECTRICAL SPECIFICATIONS Primary current 200A 1000A 1200A Current Range: Accuracy % 1.5% 0.1 to 1000A AC, continuous cycle @ ≤ 1kHz Phase shift 1.5°...
  • Page 3: Safety Specifications

    Magnetic field at 50/60 Hz IEC 1000-4-8 2.05” (52 mm) Envelope Protection: IP 40 (IEC 529) ORDERING INFORMATION Drop Test: AC Current Probe SR631 ....Cat #2113.47 1 m (IEC 68-2-32) AC Current Probe SR632 ....Cat #2114.79 Mechanical Shock: 100 g (IEC 68-2-27) Accessories: Vibration: Leads, set of 2, 5 ft.
  • Page 4 The current probe is warranted to the owner for a period of one year from the date of original purchase ® against defects in manufacture. This limited warranty is given by AEMC Instruments, not by the distributor from whom it was purchased. This warranty is void if the unit has been tampered with, abused or if the ®...