Dip Switches - wattstopper DT-300 Installation Instructions Manual

360 grad. dual technology low voltage occupancy sensor
Table of Contents

Advertisement

DIP SWITCHES

Occupancy Logic: Switches 1, 2, 3
The DT-300 has 8 logic confi gurations for occupancy
triggers. Determine the appropriate Occupancy Logic
Option using the Trigger matrix, then set the DIP
switches accordingly.
Initial Occupancy: The method that activates a change
from "Standby" (area unoccupied and loads are off) to
"Occupied" (area occupied and loads are on).
• Both requires motion detection by the PIR and the
Ultrasonic.
• Either requires motion detection by only one
technology.
• PIR requires motion detection by the PIR.
• Ultra requires motion detection by the Ultrasonic.
• Man. requires activation of the Manual Switch. (See
"Manual On Functions" for further information.)
Maintain Occupancy: The method indicating that the
area is still occupied and the lights should remain on.
Re-trigger: After the time delay elapses and the lights
turn off, detection by the selected technology within
the number of seconds indicated turns the lights back
on.
Time Delay: Switches 4, 5, 6
The sensor holds the lights on as long as occupancy
is detected. The time delay countdown starts when
no motion is detected. After no motion is detected for
the length of the time delay, the sensor will turn the
lights off. The sensor can select the time delay using
SmartSet, or you can select a fi xed time delay.
• SmartSet records occupancy patterns and uses this
history to choose an optimal time delay from 5 to
30 minutes. SmartSet behavior starts immediately
and is refi ned continually as history is collected.

Walk-through mode turns the lights off three
minutes after the area is initially occupied, if no
motion is detected after the fi rst 30 seconds. If
motion continues beyond the fi rst 30 seconds, the
selected time delay applies.
Logic Confi guration Chart
Trigger
Standard
Either
Either(5)
Both
Option 1
Either
Either
Either(5)
Option 2
PIR
Either
Either(5)
Option 3
Both Both
Both(5)
Option 4
PIR
PIR
PIR(5)
Option 5
Ultra(5)
Ultra
Ultra
Option 6
Man.
Either(30)
Either
Option 7
Man.
Both
Both(30)
Switch#
= ON
Logic
1 2 3
= OFF
Standard
Option 1
Option 2
Option 3
Option 4
Option 5
Option 6
Option 7
Time Delay
4 5 6
5 sec/SmartSet
5 minutes
10 min.
10 minutes
15 min.
15 minutes
20 minutes
30 min.
= walk-through mode
LEDs
7
Disabled
Enabled
PIR Sensitivity
8
Minimum
Max./SmartSet

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents