Relay (1-8) Output Menus - Bleed Volume Based On Makeup Volume - Walchem WebMaster ONE Instruction Manual

Water treatment controller
Hide thumbs Also See for WebMaster ONE:
Table of Contents

Advertisement

6.32

Relay (1-8) Output Menus - Bleed Volume based on Makeup Volume

This page is used to activate the relay until a programmed volume of water flows through the
bleed water meter(s). The relay activation is triggered by a programmed volume of makeup water
flowing through the makeup water meter(s)
You may also change the Relay Control Mode here. If you do, you will have to reselect the Input
Assignment as well.
This section assumes that the Relay Control Mode is set to Bleed Volume based on Makeup
Volume. Other control mode types are described in other sections of the manual.
Relay Control Mode
Click on the arrow of the pull down menu and select the way that you want to control the relay.
See Section 6.2 for details on each control mode.
Assign Makeup Meter 1, 2 or 3
Click on the arrow of the pull down menu to select the flow meter input to be used to activate this
relay. Up to 3 flow meters may be assigned.
Assign Bleed Meter 1 or 2
Click on the arrow of the pull down menu to select the flow meter input to be used to activate this
relay. Up to 3 flow meters may be assigned.
Status
This displays the current status of the relay output, either "Off" or "On", and if on, the amount of
time it has been on. Possible status messages are Off, Off/Manual, On/Time counting down and
On/Time counting down/Hand (for manual activation). The only possible error messages are
Interlock, Timeout and Sensor Error. See section 8.1 for a complete description of error messages.
Custom Name
This menu allows you to call the output another name if desired. Type the new name in the text
box.
Accumulated Makeup
This displays the volume of makeup water that has accumulated since the last time the relay
activated.
Accumulated Bleed
This displays the volume of bleed that has accumulated since the last time the relay activated.
Bleed Volume per Makeup Volume
Type the amount of water to bleed after the amount of makeup water comes in that is programmed
below.
Makeup Volume
Type the amount of makeup water that will trigger the bleed relay.