Walchem WebMaster ONE Instruction Manual page 104

Water treatment controller
Hide thumbs Also See for WebMaster ONE:
Table of Contents

Advertisement

intended to prevent the output from running out of control if the input fails in such a way that it
will never deactivate the relay.
Note that the relay will not activate again until someone resets the timer!
It will take some experience to find out what the normal output on-time will be. If the relay cycles
open and closed under worst case conditions in 30 minutes, you may want to set the Output Time
Limit at 60 minutes.
Output Mode
Click on the radio buttons to manually control the relay. The normal selection will be Auto, where
the controller uses the various set points to open and close the relay. You can force the relay closed
regardless of the set points by selecting Hand, or force the relay open regardless of the set points
by selecting Off.
If you select Off, the relay will not activate again until either Hand or Auto is selected (or if power
is cycled)! If you select Hand, the relay will activate until either Auto or Off is selected, or until
the Hand Time Limit (programmed in the next menu) expires or until the controller power is
cycled.
The Off mode is handy to prevent the relay from activating while you are changing set points. The
Hand mode is handy to be able to test the pump or valve, wiring, etc without needing to change set
points.
Hand Time Limit
Type in the text box the maximum number of minutes that the relay can be activated in the Hand
mode. Any value between 1 and 1440 is acceptable.
Click on the "Submit" button to save the changes.
Event Log
Click on the link to view the event log. The event log contains the date and time of each relay
activation and deactivation, as well as the state of each Interlock, Level Switch, or Generic digital
input.