REMEHA P 420 Installation And Service Manual page 10

Fuel oil/gas boilers
Hide thumbs Also See for P 420:
Table of Contents

Advertisement

4.3.3
Ventilation
The location of air inlets in relation to the high ventilation openings
shall ensure that the air is renewed in the entire volume of the boiler
room.
It is in any case imperative to conform to the local regulations in force.
10
Caution:
In order to avoid damage to the boiler, it is necessary to prevent the
contamination of combustion air by chlorine and/or fluoride
compounds, which are particularly corrosive.
These compounds are present, for example, in aerosol sprays,
paints, solvents, cleaning products, washing products, detergents,
glues, snow clearing salts, etc.
Therefore:
Do not pull in air evacuated from premises using such products:
hairdressing salons, dry cleaners, industrial premises (solvents),
premises containing refrigeration systems (risk of refrigerant
leakage), etc.
Do not stock such products close to the boilers.
If the boiler and/or peripheral equipment are corroded by such
chloride or fluoride compounds, the contractual guarantee
cannot be applied.
P 420
16/03/2016 - 300016839-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents