• When the function is set to extension leads test while pressing Select
switch, Power on leakage current test will be carried out instead of
Insulation resistance test.
  ・ Protective conductor resistance between accessible conductive parts and
connection of protective earth.
  ・ Leakage Current test: Measure a leakage current by actually operating
the appliance.
Extension Leads Test (Select the Leakage current test) Flowchart
(1). Protective conductor resistance test.
Light up in green
(2). Power on Leakage current test
Light up in green
Value of (1). and (2). will be
alternately displayed on the LCD.
• When the terminal is open or the resistance value exceeds measuring
range, "OL" mark (over range display) appears on the LCD.
• The test will stop. A message "Stp" appears on the LCD but values of
Leakage current aren't displayed.
Start
RPE < = 1Ω?
Yes
Brief indications " S-" and " on" will be displayed
in turns on the LCD for 5 sec and prompt the
5sec
user to set the DUT switch on.
Then a mark indicating working DUT function
will be displayed for 10 sec.
10sec
LEA < = 1mA?
Yes
PASS
# CAUTION
— 22 —
No
"no" → "Con" → "value" will
be repeated on the LCD.
No
Stop the test and
"no" → "LEA" → "value" will
be repeated on the LCD.
Light up in red
Light up in red