4.2 Commissioning and startup wizard

4.2.1 Commissioning steps:

1. Read safety instructions on page 1
2. Secure the grounding and check that cables
comply with requirements
3. Check quality and quantity of cooling air
4. Check that all start / stop switches are in
STOP position
5. Connect the drive to mains
6. Run the Startup wizard and set all necessary
parameters
Table 3: Commissioning steps

4.2.2 Startup wizard

Vacon 20 runs the startup wizard in first power-up. The wizard can be run by setting
SYS Par.4.2 =1. The following figures show the procedure.
NOTE! Running the startup wizard will always return all parameter
NOTE! StartUp-Wizard can be skipped after pressing STOP button
4
7. Perform test run without motor, see the
User Manual at
knowledge-center/technical-documentation/
8. Run no-load tests without motor being con-
nected to the process
9. Perform an identification run (Par. ID631)
10. Connect the motor to the process and per-
form test run once again
11. Vacon 20 is now ready for use
settings to their factory defaults!
continuously for 30 seconds
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
navigation & startup
http://drives.danfoss.com/