Commissioning
8.3.2
Basic parameters (Control keypad: Menu P2
Code
Parameter
P2.1.1
Min frequency
P2.1.2
Max frequency
P2.1.3
Acceleration time 1
P2.1.4
Deceleration time 1
P2.1.5
Current limit
Nominal voltage of
P2.1.6
the motor
Nominal frequency
P2.1.7
of the motor
Nominal speed of
P2.1.8
the motor
Nominal current of
P2.1.9
the motor
P2.1.10
Motor cosϕ
P2.1.11
Start function
P2.1.12
Stop function
P2.1.13
U/f optimisation
P2.1.14
I/O reference
P2.1.15
AI2 signal range
24-hour support: +358-40-8371 150 • Email: vacon@vacon.com
Min
Max
Unit
0,00
Par. 2.1.2
Hz
Par. 2.1.1
320,00
Hz
0,1
3000,0
s
0,1
3000,0
s
0,1 x I
1,5 x I
A
L
L
180
690
V
30,00
320,00
Hz
300
20 000
rpm
0,3 x I
1,5 x I
A
L
L
0,30
1,00
0
1
0
1
0
1
0
5
1
4
B2.1)
Default
Cust
ID
0,00
101
50,00
102
1,0
103
1,0
104
I
107
L
NXL2:230V
110
NXL5:400V
50,00
111
1440
112
I
113
L
0,85
120
0
505
0
506
0
109
0
117
2
390
vacon • 85
Note
NOTE: If f
> than the
max
motor synchronous speed,
check suitability for motor
and drive system
NOTE: Formulas apply
approximately for
frequency converters up to
MF3. For greater sizes,
consult the factory.
Check the rating plate of
the motor
The default applies for a 4-
pole motor and a nominal
size frequency converter.
Check the rating plate of
the motor
Check the rating plate of
the motor
0=Ramp
1=Flying start
0=Coasting
1=Ramp
0=Not used
1=Automatic torque boost
0=AI1
1=AI2
2=Keypad reference
3=Fieldbus reference
(FBSpeedReference)
4=Motor potentiometer
5=AI1/AI2 selection
Not used if AI2 Custom
min > 0% or AI2 custom
max. < 100%
1=0mA – 20mA
2=4mA – 20mA
3=0V – 10V
4=2V – 10V
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents