Figure 26 Shipping Split, 750Kva Liebert Nxl With Static Bypass (Sms/1+N) - Emerson Liebert NXL Installation Manual

500-750, 60hz, three-phase, single-module & multi-module
Table of Contents

Advertisement

Figure 26 Shipping Split, 750kVA Liebert NXL with static bypass (SMS/1+N)

PART A - WIRE STARTING POINT
Low Voltage Wire Connections Between Parts A and B
Wires are coiled and tied in Part A.
Uncoil, route and connect wires in finish part as shown.
Use wire label as guide for "TO" component, connection ID and wire part number.
Tie wires away from sharp edges, busbar and electronic components.
Detail A
531985G1
531988G2
531983G1
02-806704-
PHASE A
531985G2
02-806704-
PHASE B
531985G3
531984G1
531988G1
532061G1
532062G1
02-806704-
PHASE C
M10 FLAT WASHER
M10 RIBBED WASHER (x2)
M10 HEX HEAD BOLT
LOOSEN HARDWARE TO ALLOW
BUSBAR TO MOVE TO JOIN TO
PART B BUSBAR.
RETIGHTEN AND TORQUE TO
27 N-m (240 in-lbs)
37
PART B - WIRE FINISHING POINT
DETAIL A
DC Power Connection Between Parts A and B
Hardware Provided With Part B.
(4) Bolts Total.
Torque Connection to 27 N-m (240 in-lb).
Installation Drawings
02-806707-
02-806705-
02-806716-
F42 & F43
(-) DC BUSBAR
(+) DC BUSBAR

Advertisement

Table of Contents
loading

Table of Contents