Figure 25 Shipping Split 750Kva Liebert Nxl Without Static Bypass - Emerson Liebert NXL Installation Manual

500-750, 60hz, three-phase, single-module & multi-module
Table of Contents

Advertisement

Figure 25 Shipping split 750kVA Liebert NXL without static bypass

Part A (Rectifier) - Wire Starting Point
Low-Voltage Wire Connections
Between Part A and Part B
Wires are coiled and tied in Part A.
Uncoil, route and connect wires in finish part as shown.
Use wire label as guide for "to" component, connection
ID and wire part number. Tie wires away from sharp
edges, busbar and electronic components.
Note:
See Page 2 of 2, drawing
# U40-7g-2001
Part A (Rectifier) - Wire Finishing Point
Low Voltage Wire Connections Between Part B and Part A
Wires are coiled and tied in Part B.
Uncoil, route and connect wires in finish part as shown.
Use wire label as guide for "to" component, connection ID and wire part number.
Tie wires away from sharp edges, busbar and electronic components.
A
531985GI
531988G2
531983G1
02-806704-
Phase A
531985G2
02-806704-
Phase B
531985G3
532061G1
02-806704-
Phase C
Part B (Inverter) - Wire Finishing Point
Detail A
DC Power Connection Between Part A and Part B
Hardware Provided With Part B: 4 Bolts Total
Torque Connection To 27 N-m (240 In-lbs)
M10 Flat Washer
M10 Ribbed Washer (2x)
M10 Hex Head Bolt
Loosen hardware to allow
busbar to move to join
to Part B Busbar.
Retighten and torque
to 27 N-m (240 in-lb)
532049G1
532065G1
02-806710-
532063G1
532065G1
02-806708-
Part B (Inverter) - Wire Starting Point
36
Installation Drawings
(-) DC Busbar
(+) DC Busbar
U40-7g-2000
Pg. 1, Rev. 01
NOTE:
See Page 1 of 2, drawing
# U40-7G-2000
U40-7G-2001
Rev. 1
02-806707-
Hardware
for Detail A
Included
in This Box
02-806716-

Advertisement

Table of Contents
loading

Table of Contents