Technical Data; Protocol - Viessmann KW10 Installation, Start-Up And Service Instructions Manual

Vitotronic 100 boiler control unit for modulating temperature heating systems
Table of Contents

Advertisement

Additional Information

Technical Data

Protocol

Please indicate settings
which have been altered ...
Factory default settings
H Fixed high limit "
" set to 230
H Adjustable high limit "
30
°
F / 110
°
C
" set to 167
°
F / 75
°
C
Power:
Burner switching capacity:
Room thermostat:
Anticipator setting:
Fixed high limit:
Adjustable high limit:
Pump output:
Outdoor temperature sensor:
Allowable ambient temperature:
H operation:
H storage and transport:
Altered settings
Altered to 212°F / 100°
j
Altered to 189°F / 87°C
j
120 VAC
1 Phase
60 Hz
15 A pre-fuse
120 VAC
2.5 FLA
24 VAC
0.1 A
230°F / 110°C max.
(fixed)
167 to 239°F max.
75 to 115°C max.
(adjustable)
120 VAC
1 Phase
60 Hz
3 FLA
10 kilo Ohms at
77°F / 25°C
max. wire length
up to 1000 ft. / 300 m
32 to 104°F
0 to 40°C
-4 to 149°F
-20 to 65°C
C