Vitotronic 100, KW10B Installation, Start-up and Service

Technical Data

Technical Data
Power: 120 VAC, 1 Phase, 60 Hz, 15A pre-fuse
Burner switching capacity: 120 VAC, 2.5A (full load)
Room thermostat: 24 VAC
Anticipator setting: 0.1 A
Fixed high limit: 230° F (110° C) max. (fixed)
Adjustable high limit: 167° F to 239° F max.
75° C to 115° C max. (adjustable)
Boiler & DHW Pump output: 120 VAC, 1 Phase, 60 Hz,
Outdoor temperature sensor: 5k Ohms at 77° F (25° C)
Boiler temperature sensor: 10K
DHW temperature sensor: 10K
Allowable ambient temperature
operation: 32° F to 104° F (0° C to 40° C)
g
storage and transport: -4° F to 149° F (-20° C to 65° C)
g

Protocol

Please indicate settings which have been altered ...
Factory default settings
Fixed high limit "E" set to 230° F (110° C)
g
Adjustable high limit "R" set to 167° F (75° C)
g
3A (full load)
max. wire length up to
95 ft. (35 m)
Altered settings
Altered to 212° F (100° C)
Altered to 189° F (87° C)
Additional Information