Grounding; Thermostat / Low Voltage Connections - Maytag *TC Installation Instructions Manual

Two-stage condensing gas furnaces with fixed & variable speed blowers - 95.1 % afue
Table of Contents

Advertisement

IMPORTANT NOTES:
• An electrical disconnect must be installed readily
accessible from and located within sight of the
furnace. See Figure 23 or the wiring diagram label
inside of the control door. Any other wiring methods
must be acceptable to authority having jurisdiction.
• Proper line voltage polarity must be maintained in
order for the control system to operate correctly.
Verify the incoming neutral line is connected to the
white wire and the incoming HOT line is connected
to the black wire. The furnace will not operate unless
the polarity and ground are properly connected as
shown in Figure 23.
• If replacing any of the original wires supplied with
the furnace, the replacement wire must be copper
wiring and have a temperature rating of at least
105°F (40°C). For electrical specifi cations, refer to
the furnace nameplate or Table 5.
Furnace
Cabinet
Input
(Btuh)
60,000
80,000
100,000
120,000
Thermostat Wire Gauge
24
22
20
18
*
Time-delay fuses or circuit breakers are required.
Field Supplied
Fused Service
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Nominal
Maximum
Width
Electrical
Operating
(in.)
Supply
Voltage
17 ½
115-60-1
21
115-60-1
21
115-60-1
24 ½
115-60-1
2 - wire - Heating
Table 5. Wire Length & Voltage Specifi cations
Field Supplied
Disconnect w/in
Panel
Sight of Furnace
Black
White
Ground
Field Line Voltage Wiring
Factory Line Voltage Wiring
Figure 23. Line Voltage Field Wiring

Grounding

To minimize personal injury, the furnace cabinet
must have an uninterrupted or unbroken
electrical ground. The controls used in this
furnace require an earth ground to operate
properly. Acceptable methods include electrical
wire or conduit approved for ground service.
Do not use gas piping as an electrical ground!

Thermostat / Low Voltage Connections

• The furnace is designed to be controleed by a 24 VAC
thermostat. The thermostat's wiring must comply with
the current provisions of the NEC (ANSI/NFPA 70) and
with applicable local codes having jurisdiction.
• NORDYNE no longer supports twinning of two stage
furnaces. Please contact your furnace distributor for
details.
• The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Minimum
Maximum
Operating
Voltage
Amperes
127
103
127
103
127
103
127
103
Recommended Thermostat Wire Length
55 ft.
90 ft.
140 ft.
225 ft.
Junction Box (may be int. or ext.
to the furnace). These connections
can be made in the field supplied
disconnect at the furnace.
Black
White
Ground
Field Supplied
Panel Connector
WARNING:
Minimum
Furnace
Wire
Gauge
7.0
14
9.4
14
9.4
14
12.5
14
4 or 5 wire - Cooling
25 ft.
45 ft.
70 ft.
110 ft.
Black
White
Ground
Maximum
Fuse or Circuit
*
Breaker Amps
15
20
20
25
25