Maytag Amana CVC96 Series Installation Instructions Manual
Maytag Amana CVC96 Series Installation Instructions Manual

Maytag Amana CVC96 Series Installation Instructions Manual

Two-stage gas furnace
Table of Contents

Advertisement

Quick Links

I
NSTALLATION
*CVC96 & *MVC96
T
-S
WO
TAGE
(Type FSP CATEGORY IV Direct
or Non Direct Vent Air Furnace)
These furnaces comply with requirements em-
bodied in the American National Standard / Na-
tional Standard of Canada ANSI Z21.47·CSA-2.3
Gas Fired Central Furnaces.
s a professional installer you have an obligation to know
A
the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself
with this Instruction Manual. Pay special attention to all
safety warnings. Often during installation or repair it is
possible to place yourself in a position which is more
hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product
safely and to know it well enough to be able to instruct a
customer in its safe use.
Safety is a matter of common sense...a matter of thinking
before acting. Most dealers have a list of specific good
safety practices...follow them.
The precautions listed in this Installation Manual are intended
as supplemental to existing practices. However, if there is
a direct conflict between existing practices and the content
of this manual, the precautions listed here take precedence.
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
NOTE: Please contact your distributor or our website for
*
the applicable Specification Sheet referred to in this manual.
IOG-2008D
10/15
I
NSTRUCTIONS FOR
G
F
AS
URNACE
Installer:
Affix all manuals
adjacent to the unit.
5151 San Felipe Suite 500
Houston, TX 77056
www.goodmanmfg.com • www.amana-hac.com
© 2014-2015 Goodman Manufacturing Company, L.P .
is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .................................... 3
.......................................... 4
........................................... 5
PRODUCT DESCRIPTION ....................................... 5
.................................................... 5
PRODUCT APPLICATION ....................................... 5
........................................ 9
INSTALLATION POSITIONS ................................... 10
........................................ 10
...................................... 10
................................................... 10
A
V
/F
.................................................. 11
......................................... 11
D
C
P
V
/F
ROPER
ENT
LUE AND
...................................... 13
V
V
............................................ 14
........................................ 14
V
V
V
V
& C
A
V
T
NTAKE
ERMINATIONS
D
V
F
IRECT
ENT
URNACES
V
S
W
V
........................................ 19
IDE
ALL
ENT
G
D
I
ENERAL
RAIN
NFORMATION
F
D
....................................... 19
IELD
RAIN
U
M
I
PFLOW
ODEL
NSTALLED
E
R
XITING
IGHT
.................. 4
................................. 8
................................... 8
............... 10
C
A
C
IR
ONNECTIONS
C
............ 11
ONNECTIONS
-D
/D
V
............... 12
............................. 12
C
OMBUSTION
............................ 14
............................. 14
............................. 15
...................... 16
............................... 16
I
M
EASUREMENTS FOR
) .......... 18
F
I
OR
NSTALLATION OF
................................... 19
............................... 19
................................. 19
V
........................ 20
ERTICALLY
................................... 20
..... 10
..... 13

Advertisement

Table of Contents
loading

Summary of Contents for Maytag Amana CVC96 Series

  • Page 1: Table Of Contents

    Specification Sheet referred to in this manual. 5151 San Felipe Suite 500 IOG-2008D Houston, TX 77056 10/15 www.goodmanmfg.com • www.amana-hac.com © 2014-2015 Goodman Manufacturing Company, L.P . is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.
  • Page 2 ........20 CTK0* WIRING ..........43 RAIN XITING ....44 PFLOW ODEL NSTALLED ORIZONTALLY OMFORT YSTEM DVANCED EATURES ........21 ......45 WITH IGHT URNACE DVANCED EATURES ENUS .. 21 .......... 47 PFLOW MODEL INSTALLED HORIZONTALLY WITH LEFT SIDE DOWN HERMOSTAT ....
  • Page 3: Safety Considerations

    AFETY ONSIDERATIONS WARNING Adhere to the following warnings and cautions when install- O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER ing, adjusting, altering, servicing, or operating the furnace. INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE To ensure proper installation and operation, thoroughly read REFER TO THIS MANUAL OR ADDITIONAL ASSISTANCE OR this manual for specifics pertaining to the installation and...
  • Page 4: Shipping Inspection

    RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE Advertencia especial para la instalación de calentadores ó manejadoras de aire en áreas cerradas como estacionamientos ó cuartos de servicio. Cette ventilation est nécessaire pour éviter le danger d'intoxication Las emisiones de monóxido de carbono pueden circular a través au CO pouvant survenir si un appareil produisant du monoxyde del aparato cuando se opera en cualquier modo.
  • Page 5: Product Description

    1. Disconnect all power to the furnace. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground. 2. Firmly touch a clean, unpainted, metal surface of the furnaces near the control. Any tools held in a person’s hand during grounding will be discharged.
  • Page 6: Location Requirements & Considerations

    • Return air ducts are provided and sealed to the furnace. • A return air temperature range between 60ºF (16ºC) and 80ºF (27ºC) is maintained. • Air filters are installed in the system and replaced daily during construction and upon completion of construction. •...
  • Page 7 piping system from furnace to termination can be accomplished within the guidelines given. NOTE: The length of flue and/ or combustion air piping can be a limiting factor in the location of the furnace. • Locate the furnace so condensate flows downwards to the drain. Do not locate the furnace or its condensate drainage system in any area subject to below freezing temperatures without proper freeze protection.
  • Page 8: Clearances And Accessibility

    • Counterflow Installation over a combustible floor. If installation over a combustible floor *M VC96 M INIMUM CLEARANCES TO COM BUSTIBLE MATERIALS becomes necessary, use an accessory subbase (INCHES) (see Specification Sheet applicable for your POSITION* SIDES REAR FRONT BOTTOM FLUE model for details.) A special accessory subbase must be used for upright counterflow unit...
  • Page 9: Combustion & Ventilation Air Requirements

    1. Seal any unused openings in the venting system. 2. Inspect the venting system for proper size and horizontal pitch, as required by the National Fuel Gas Code, ANSI Z223.1 or the Natural Gas and Propane Installation Code, CSA B149.1-05 and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
  • Page 10: Installation Positions

    NSTALLATION OSITIONS This furnace may be installed in an upright position or horizontal on either the left or right side panel. Do not install this furnace on its back. For upright upflow furnaces, return air ductwork may be attached to the side panel(s) and/or basepan. For horizontal upflow furnaces, return air ductwork must be attached to the basepan.
  • Page 11: Alternate Electrical And Gas Line

    When using the horizontal alternate vent configuration, you must use the RF000142 vent drain kit. See following illustration. Figure 3B Alternate Vent/Flue Location Figure 3A Figure 3C LTERNATE LECTRICAL AND ONNECTIONS Recommended Installation Positions This furnace has provisions allowing for electrical and gas line connections through either side panel.
  • Page 12: Vent/Flue Pipe & Combustion Air Pipe

    & C OMBUSTION WARNING WARNING PON COMPLETION OF THE FURNACE INSTALLATION CAREFULLY AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF THE INJURY OR DEATH AREFULLY READ AND FOLLOW ALL INSTRUCTIONS FURNACE TO ASSURE IT IS PROPERLY SEALED EAKS IN THE FLUE GIVEN IN THIS SECTION...
  • Page 13: Termination Locations

    All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/16” minimum from the plane of one opening to the center line of the other opening for 2”...
  • Page 14: Canadian Venting Requirements

    • The vent termination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter a building (door, window, or gravity air inlet). • The vent termination of vent pipe run vertically through a roof must terminate at least 12 inches above the roof line (or the anticipated snow level) and be at least 12 inches from any vertical wall (including any anticipated snow build up).
  • Page 15: Non -Direct Vent Installations

    COMBUSTION AIR INTAKE OPTION: The RF000142 coupling can be secured directly to the furnace intake coupling if conden- sation is a concern. If the RF000142 is used on the combustion air inlet, it must be installed with the arrow pointing up. It should be noted, the combustion air will actually be moving in a direction opposite of the arrow on the RF000142 coupling.
  • Page 16: Non -Direct Vent (Single Pipe ) Piping

    IRECT INGLE IPING CAUTION Non-direct vent installations require only a vent/flue pipe. The E SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS vent pipe can be run horizontally with an exit through the side of WHEN REINSTALLING COUPLING AND SCREWS the building or run vertically with an exit through the roof of the building.
  • Page 17 DOWN VENTING UPFLOW MODEL FURNACES ONLY Use alternate vent & combination air locations Vent Pipe 6’ MAX. Combustion Air Pipe Both Pipes Terminated Outside Structure Field Supplied Drain Tee on Vent Pipe 1/4” per foot min. slope Condensate trapped to prevent flue gas from escaping and routed to field supplied condensate disposal All piping and fittings must be joined per material manufacturer’s specifications...
  • Page 18: Ent Ombustion Ir Ntake

    IRECT IPING 12" MIN. Direct vent installations require both a combustion air intake and a vent/ flue pipe. The pipes may be run horizontally and exit through the side of the VENT/FLUE TEE ( OPTIONAL) building or run vertically and exit through the roof of the building. The 45°...
  • Page 19: Condensate Drain Lines & Drain Trap

    NTAKE ERMINATIONS NSTALLATION OF ULTIPLE IRECT URNACES If more than one direct vent furnace is to be installed vertically through 3”MIN a common roof top, maintain the same minimum clearances be- 24”MAX tween the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit.
  • Page 20: Side

    primed before initial furnace start up. When an air conditioning coil drain is connected to the field supplied furnace drain, it must be vented, with an open tee installed at a height no higher than the bottom of the furnace collector box to prevent air conditioning con- densate from backing up into the furnace if the common drain was blocked.
  • Page 21: Pflow Odel Nstalled

    4. Install smaller end of hose #3 on 45º elbow and secure with 1" clamp. 5. Refer to Field Supplied Drain section for instructions on field supplied / installed drain on outlet of furnace trap. PFLOW ODEL NSTALLED ORIZONTALLY WITH IGHT Minimum 5 ½"...
  • Page 22: Counter Flow Model Installedv

    12. Use two silver clamps and secure the hoses to drain trap. The trap outlet faces the front of the furnace. Secure the trap to the cabinet using two screws removed in step 2 by inserting the two screws through the large set of holes in the top mounting tabs of the trap into the two predrilled holes in the side of the cabinet.
  • Page 23: Ounterflow Odel Nstalled

    6. Mate the trap inlets to the hoses, the outlet of the trap must face the original bottom of the furnace. Secure with silver clamps. 7. Fasten the drain trap to the cabinet with two screws removed in step 2 8.
  • Page 24: Junction Box Relocation

    Use a separate fused branch electrical circuit containing properly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating plate. An electrical disconnect must be provided at the furnace location.
  • Page 25: Single -Stage Heating Thermostat

    This furnace is equipped with a 40 VA transformer to facilitate use with most cooling equipment. Consult the wiring diagram, located on the blower compartment door, for further details of 115 Volt and 24 Volt wiring. NOTE: For single stage cooling applications, a jumper may be required between Y1 and Y2 at the furnace control in order to achieve the desired single stage cooling airflow.
  • Page 26: Fossil Fuel Applications

    To install/connect a dehumidistat: 1. Turn OFF power to furnace. 2. To enable the dehumidify function on the integrated control module, set the dehumidification ENABLE dip switch from OFF to 3. Secure the dehumidistat neutral wire (typically the white lead) to the terminal marked “DEHUM” on the furnace integrated control module.
  • Page 27: 115 Volt Line Connection Ofa

    transformer wire would be connected to the Line N on the control board.The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts whenever the circulator blower is energized. In addition, the control is equipped with a dedicated humidification relay which is avail- able through ¼...
  • Page 28: Gas Supply And Piping

    and opens when the water level in the evaporator coil base pan reaches a particular level. The control will respond by turning off the outdoor compressor and display the proper fault codes. If the AUX switch is detected closed for 30 seconds, normal operation resumes and error messages are no longer displayed.
  • Page 29: Gas Piping Connections

    IPING ONNECTIONS WARNING The gas piping supplying the furnace must be properly sized based O AVOID POSSIBLE UNSATISFACTORY OPERATION OF EQUIPMENT on the gas flow required, specific gravity of the gas, and length of DAMAGE DUE TO UNDERFIRING OR EQUIPMENT USE THE PROPER SIZE the run.
  • Page 30 – Manual Shut Off Valve Alternate Semi-rigid metallic tubing and metallic fittings. Manifold Burners (upstream from Gas Line Aluminum alloy tubing must not be used in exterior locations. ground joint Location pipe union) In order to seal the grommet cabinet penetration, rigid pipe must be used to reach the outside of the cabinet.
  • Page 31: Propane Gas Tanks And Piping

    IPING HECKS Before placing unit in operation, leak test the unit and gas connec- tions. WARNING Check for leaks using an approved chloride-free soap and water O AVOID THE POSSIBILITY OF EXPLOSION OR FIRE NEVER USE A MATCH solution, an electronic combustible gas detector, or other approved OR OPEN FLAME TO TEST FOR LEAKS testing methods.
  • Page 32: Circulating Air & Filters

    & F IRCULATING ILTERS UCT WORK Duct systems and register sizes must be properly designed for the CFM and external static pressure rating of the furnace. Design the ductwork in accordance with the recommended methods of “Air Conditioning Contractors of America” Manual D. Install the duct system in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems.
  • Page 33: Pflow Models ]

    OTTOM ETURN PENING PFLOW ODELS The bottom return air opening on upflow models utilizes a “lance and cut” method to remove sheet metal from the duct opening in the base pan. To remove, simply press out the lanced sections by hand to expose the metal strips retaining the sheet metal over the duct opening.
  • Page 34: Bottom Return Air Opening

    Refer to the following table to determine filter area require- ments. Filter Sizing Chart Model Minimum Recommended Filter Size PRIGHT NSTALLATIONS *MVC960403BN** 1 - 16 X 25 Side or Bottom Depending on the installation and/or customer preference, dif- *MVC960603BN** 1 - 16 X 25 Side or Bottom fering filter arrangements can be applied.
  • Page 35: Startup Procedure & Adjustment

    The following figure shows possible filter locations. FILTER AIR FLOW ACCESS DOOR CENTRAL RETURN GRILLE SIDE RETURN EXTERNAL FILTER RETURN RACK KIT CENTRAL DUCT (EITHER SIDE) RETURN GRILLE FILTER SUPPORT BRACKET (Field Supplied) Possible Upright Upflow Figure 44 AIR FLOW Possible Upright Counterflow Filter Locations...
  • Page 36: Gas Supply Pressure Measurement

    11. Adjust the thermostat to a setting above room temperature. 12. After the burners are lit, set the thermostat to desired temperature. URNACE HUTDOWN 1. Set the thermostat to the lowest setting. The integrated control will close the gas valve and extinguish flame. Following a 15 second delay, the induced draft blower will be de-energized.
  • Page 37 Open to Atmosphere High Fire Regulator Outlet Adjust Regulator Pressure Boss Vent White-Rodgers Model 36J54 (Two-Stage) Low Fire Regulator Figure 46A Adjust Inlet Pressure Boss High Fire Common Regulator Regulator Terminal(C) Adjust Vent White-Rodgers Model 36J54 Connected to Manometer Figure 46B Common Terminal(C) High Fire Coil...
  • Page 38: Gas Manifold Pressurem

    ANIFOLD RESSURE EASUREMENT AND DJUSTMENT Gas Line Only small variations in gas pressure should be made by adjusting the gas valve pressure regulator. The manifold pressure must be measured with the Shutoff burners operating. To measure and adjust the manifold pressure, use the Valve following procedure.
  • Page 39: Temperature Rise

    EXAMPLE: If it took 23 seconds to complete one revolution of the 1/2 ft. dial (23 x 2 = 46). This tells us that at this rate, it would take 46 seconds to consume one cu. ft. of gas. 3600 / 46 = 78. This tells us that in one hour, the furnace would consume 78 cu.
  • Page 40 The cooling system manufacturer’s instructions must be checked for required air flow. Any electronic air cleaners or other devices may require specific air flows, consult installation instructions of those devices for requirements. 3. Knowing the furnace model, locate the high stage cooling air flow charts in the Specification Sheet applicable to your model. Look up the cooling air flow determined in step 2 and find the required cooling speed and adjustment setting.
  • Page 41 Sw itch Bank: S3 Sw itch Bank: S3 DIP Sw itch No. DIP Sw itch No. Adjust Taps Cooling Speed Taps + 5%* - 5% + 10% - 10% (*Indicates factory setting) (*Indicates factory setting) • Profile D ramps up to 50% of the demand for 1/2 minute, then ramps to 85% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes.
  • Page 42: Blower Heat Off Delay Timings

    7. Select the heating speed for your model from the heating speed chart in the Specification Sheet. The adjust setting (already established by the cooling speed selection) determines which set of speeds are available. The selected speed must provide a temperature rise within the rise range listed with the particular Sw itch Bank S4 model.
  • Page 43: Airflow Considerations

    IRFLOW ONSIDERATIONS Airflow demands are managed differently in a fully communi- cating system than they are in a non-communicating wired sys- System Airflow Dem and tem. The system operating mode (as determined by the ther- System Operating Mode Source mostat) determines which unit calculates the system airflow demand.
  • Page 44: Omfort Et Ystem Dvanced

    UTDOOR NDOOR IRING Two wires can be utilized between the indoor and outdoor units. For this wiring scheme, only the data lines, 1 and 2, are needed between the indoor and outdoor units. A 40VA, 208/230 VAC to 24VAC transformer must be installed in the out- CTK0* door unit to provide 24VAC power to the outdoor unit’s Thermostat...
  • Page 45: Furnace Advanced Features Menus

    URNACE DVANCED EATURES ENUS (accessed through the communicating thermostat) C ONFIGUR ATION Subm e nu Ite m Indica tion (for Displa y Only; not Use r Modifia ble ) Number of Heat Stages (HT STG) Displays the number of furnace heating stages Input Rate (BTU/HR) Displays the furnace input rate in kBtu/hr Motor HP (1/2, ¾, or 1 MTR HP)
  • Page 46 SET-UP Subm e nu Ite m Use r Modifia ble Options Com m e nts -10% to +10% in 2% increments, Trims the heating airflow by the selected Heat Airflow Trim (HT TRM) default is 0% amount. 5, 10, 15, 20, 25, or 30 seconds, Heat ON Delay (HT ON Selects the indoor blower heat ON delay default is 30 seconds...
  • Page 47: Thermostat Menu

    HERMOSTAT If this furnace is installed with a communicating compatible heat pump, the system is recognized as a dual fuel system. The balance point temperature should be set via the thermostat. IAGNOSTICS Accessing the furnace’s diagnostics menu provides ready access to the last six faults detected by the furnace. Faults are stored most recent to least recent.
  • Page 48: Normal Sequence Of Operation

    YSTEM ROUBLESHOOTING NOTE: Refer to the instructions accompanying the ComfortNet compatible outdoor AC/HP unit for troubleshooting information. Refer to the Troubleshooting Chart in the back of this manual for a listing of possible furnace error codes, possible causes and corrective actions. AULT ECALL EQUENCE...
  • Page 49: Operational Checks

    • Circulator blower continues running for the selected heat off delay period (90, 120, 150 or 180 seconds). The speed run during this period depends on the last heat call provided by the thermostat. If the last call for heat was a call for low heat, the air circulator motor will run on low heat speed for the duration of the heat off delay period (90, 120, 150 or 180 seconds).
  • Page 50: Troubleshooting

    NTEGRATED ONTROL ODULE The integrated control module is an electronic device which, if a potential safety concern is detected, will take the necessary precautions and provide diagnostic information through an LED. RIMARY IMIT The primary limit control is located on the partition panel and monitors heat exchanger compartment temperatures. It is a normally- closed (electrically), automatic reset, temperature-activated sensor.
  • Page 51: Maintenance

    1. Automatic reset. The integrated control module will automatically reset itself and attempt to resume normal operations following a one hour lockout period. 2. Manual power interruption. Interrupt 115 volt power to the furnace. 3. Manual thermostat cycle. Lower the thermostat so that there is no longer a call for heat for 1 -20 seconds then reset to previous setting.
  • Page 52: Burners

    URNERS Visually inspect the burner flames periodically during the heating season. Turn on the furnace at the thermostat and allow several minutes for flames to stabilize, since any dislodged dust will alter the flames normal appearance. Flames should be stable, quiet, soft, and blue (dust may cause orange tips but they must not be yellow).
  • Page 53: Dip Switches

    WITCHES Dip Switch Switch Bank Purpose Function Heating Off Delay 2 Stage Stat Thermostat 1 Stg Stat 5 min delay Setup 1 Stg Stat auto delay Cooling Airflow Add 5% Minus 5% Trim Add 10% Minus 10% Ramping Profile Heating Airflow Disabled Dehum Enabled...
  • Page 54: Status Codes

    TATUS ODES INTERNAL CONTROL FAULT/NO POWER NORMAL OPERATION LOCKOUT DUE TO EXCESSIVE RETRIES LOW STAGE PRESSURE SWITCH STUCK CLOSED AT START OF HEATING CYCLE LOW STAGE PRESSURE SWITCH STUCK OPEN OPEN HIGH LIMIT SWITCH FLAME DETECTED WHEN NO FLAME SHOULD BE PRESENT OPEN FUSE LOW FLAME SIGNAL IGNITER FAULT OR IMPROPER GROUNDING...
  • Page 55: Troubleshooting Chart

    ROUBLESHOOTING HART ComfortNet™ Symptoms of Abnormal Diagnostic/ Thermostat Only Operation (Legacy & Status LED Fault Description Possible Causes Corrective Actions Notes & Cautions ComfortNet™ Thermostat) Codes Message Code • Furnace fails to operate None • No 115 power to INTERNAL •...
  • Page 56 ROUBLESHOOTING HART Symptoms of Abnormal ComfortNet™ Diagnostic/ Operation (Legacy Thermostat Only Status LED Fault Description Possible Causes Corrective Actions Notes & Cautions & ComfortNet™ Codes Message Code Thermostat) • Induced draft blower • Low stage PS1 OPEN • Pressure switch hose •...
  • Page 57 ROUBLESHOOTING HART Symptoms of Abnormal ComfortNet™ Diagnostic/ Operation (Legacy Thermostat Only Status LED Fault Description Possible Causes Corrective Actions Notes & Cautions & ComfortNet™ Codes Message Code Thermostat) • Furnace fails to operate. • Problem with IGNITER • Improperly connected •...
  • Page 58 ROUBLESHOOTING HART ComfortNet™ Symptoms of Abnormal Diagnostic/ Thermostat Only Operation (Legacy Status LED Fault Description Possible Causes Corrective Actions Notes & Cautions & ComfortNet™ Codes Message Code Thermostat) • Operation different than • Invalid memory INVALID MC • Shared data set on •...
  • Page 59 ROUBLESHOOTING HART ComfortNet™ Symptoms of Abnormal Diagnostic/ Thermostat Only Operation (Legacy Status LED Fault Description Possible Causes Corrective Actions Notes & Cautions & ComfortNet™ Codes Message Code Thermostat) • Circulator blower MOTOR • Turn power OFF prior • Furnace fails to operate. motor senses TRIPS to repair...
  • Page 60: Wiring Diagram

    IRING IAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
  • Page 61: Special Instructions For Products Installed In The State Of Massachusetts

    PECIAL NSTRUCTIONS FOR RODUCTS NSTALLED IN THE TATE OF ASSACHUSETTS For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termi- VENT/FLUE nation is less than seven (7) feet above finished grade in the area...
  • Page 62 THIS PAGE LEFT BLANK INTENTIONALLY.
  • Page 63 THIS PAGE LEFT BLANK INTENTIONALLY.
  • Page 64 Financing Options 5151 San Felipe Suite 500 Houston, TX 77056 www.goodmanmfg.com • www.amana-hac.com © 2014 - 2015 Goodman Manufacturing Company, L.P . is a registered trademark of Maytag Corporation or its related companies and is used under license. All rights reserved.

This manual is also suitable for:

Amana mvc96 seriesAmana gmvc96

Table of Contents