Okofen PE 08 Operating Manual page 162

Initial start up pellet heating system with auger delivery system or vacuum suction system for professionals
Table of Contents

Advertisement

162
Cause and Remedy:
Display:
Description:
Cause and Remedy:
Display:
Description:
Cause and Remedy:
13.5 Underpressure box (Fault 5012, 5013, 5041, 5042)
Display:
Description:
Cause and Remedy:
PE 567 EN 1.1
Sensor defect
Sensor cable defect
Sensor temperature too
low
Sensor polarity reversed
[5048] PE Burner gas open-circuit (only SMART without combustion cham-
ber sensor)
Burner gas sensor fracture, measuring circuit of Burner gas sensor is open –
Output RGF
Sensor not connected
Sensor cable defect
Sensor defect
Sensor temperature too
high
[5049] PE Burner gas short-circuit (only SMART without combustion cham-
ber sensor)
Burner gas sensor short circuit, measuring circuit of Burner gas sensor short
circuit – Output RGF
Sensor defect
Sensor cable defect
Sensor temperature too
low
Sensor polarity reversed
[5012] PE Underpressure box BS
Negative draft input open, measuring circuit from negative draft measure-
ment open – Input UP
Signal incorrect
Signal cable defect
No signal
Combustion chamber leak
Measure sensor (approx. 5 mV at 125°C) re-
place if required
Replace sensor
Sensor temperature below measuring range
(– 10°C)
Change sensor connection + and –
Connect sensor at input
Replace sensor
Measure sensor (NiCrNi) replace if required
Sensor temperature above measuring range
(1100°C)
Measure sensor (approx.. 5mV at 125°C) re-
place if required
Replace sensor
Sensor temperature below measuring range
(– 10°C)
Change sensor connection + and –
Check poarity and signal (0-10V)
Replace sensor
Replace underpressure box
Check total closure of boiler door
Malfunction report