Okofen PE 08 Operating Manual page 127

Initial start up pellet heating system with auger delivery system or vacuum suction system for professionals
Table of Contents

Advertisement

Boiler Controlled Pump
127
The Switch Off Hyst is the hysteresis for the boiler temperature minimum. It pre-
vents the clocking (ON OFF ON OFF) of the Boiler Controlled Pump.
The Run on time is the time how long the UW continues to run after the end of bur-
ner demand. – in minutes
Is the Control Range of output UW at cycling mode. The speed controller starts at
the boiler temperature minimum with a speed of 30% and increases to the boiler
temperature minimum + Control Range up to 100% speed.
Back to the menu Pellematic.
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56