Okofen PE 08 Operating Manual page 131

Initial start up pellet heating system with auger delivery system or vacuum suction system for professionals
Table of Contents

Advertisement

Output Test
Designation
Note:
only possible if the boiler control-
led pump is connected
Motor store room
the motor auger store room is running
auger
Note:
RA
On suction systems, switch on the
suction fan motor first otherwise
the motor on the store room auger
may become jammed.
Motor hopper
Note:
RES 1
PES 36–56 only
Motor burner
• the motor that feeds pellets to the
auger
ES
• the direction of rotation of the store
Combustion air
The combustion air fan is running
fan
LUFT
Anti-blowback
the fire protection flap (orange motor
system
on burner) opens
BSK
Scrubber pump
Note:
not implemented at this type of
boiler
Check if
burner is running auger is correct.
room auger is correct
If not, then check
• the store room auger motor is connected
• the auger rotates easily
• the motor is defective
• the wiring is correct
• the motor is defective
• the burner auger motor is connected
• the burner auger motor rotates easily
• the motor is defective
• the wiring is correct
• the motor is defective
• the wiring is correct
• the ball valve moves easily
• the motor is defective
• the wiring is correct
• the scrubber pump is defective
Operating Manual PELLEMATIC® PE(S)(K)(B) 10 — 56
131