4 |

CONNECT THE CABLE TO THE OUTDOOR UNIT

1 Remove the electrical control board cover from the outdoor unit by loosening the screw
2 Connect the connective cables to the terminals as identified with their respective matched numbers on the terminal block of
indoor and outdoor units
3 Secure the cable onto the control board with the cord clamp
4 To prevent the ingress of water, form a loop of the connective cable as illustrated in the installation diagram of indoor and out-
door units
5 Insulate unused cords (conductors) with PVC-tape Process them so they do not touch any electrical or metal parts
5 |
AIR pURGING AND TEST OpERATION
NOTE: Connective pipe length will affect the capacity and energy efficiency of the unit. The nominal efficiency is tested basing on the
pipe length of 5 meters.
1. Air purging
The indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncon-
densables and moisture from the system
Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected
and all wiring for the test run has been completed
Pipe length and refrigerant amount:
Connective pipe length
Less than 5 m
More than 5 m
For the R410A refrigerant model, make sure the refrigerant added into air conditioner is liquid form in any cases
When relocating the unit to another place, using vacuum pump to perform evacuation
CAUTION
Open the valve stem until it hits against the stopper Do not try to open it further
Securely tighten the valve stem cap with a spanner or the like
Valve stem cap tightening torque See
Tightening torque table
Outdoor unit
A
B
Packed valve
Cover
Cooling only type
Screw
To indoor unit
Air purging method
Use vacuum pump
Liquid side: ø 6 35 mm
Use vacuum pump
R22: (Pipe length-5) × 30 g/m
R410A: (Pipe length-5) × 20 g/m
Refrigerant
Indoor unit
Gas side
Liquid side
Flare nut
Terminal block of outdoor unit
Cooling & heating type
or
To indoor unit
To indoor unit
Additional amount of refrigerant to be charged
R22: (Pipe length-5) × 60 g/m
R410A: (Pipe length-5) × 40 g/m
Valve body
Valve stem
or
To indoor unit
Liquid side: ø 9 52 mm
Flare nut
Stopper
Cap
11
EN