Backing Up Os Project Data; Backing Up Configuration Data - Siemens SIMATIC PCS 7 Service Manual

Process control system
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Ensuring Availability
3.2 Data backup
Project and standard functions
Project functions and standard functions have the file name extension * .fct. PCS 7 saves these
functions in the following folders by default:
● Project functions in the folder "\library" of the OS project
● Standard functions in the folder "\aplib" in the installation directory of PCS 7
Local and global actions
Local and global actions have file name extension * .pas. PCS 7 saves these actions in the
following folders by default:
● Local Actions in the folder "\<Name of PC>\Pas" of the project directory
● Global actions in the "\Pas" folder of the OS project
Additional information
● Online Help for
3.2.3

Backing up OS project data

3.2.3.1

Backing up configuration data

Introduction
When you archive a multiproject, the configuration data of the PCS 7 operator station are
automatically included in the backup. A separate backup is not necessary.
Backing up OS configuration data
The configuration data for PCS 7 operator station are saved by default in the following
folder: ..\Siemens\WinCC\WinCCProjects.
Compress the current project paths in this folder as a backup and save the backup on a suitable
medium, such as a CD.
Backing up OS PC data
The OS configuration data are located on the PCS 7 engineering station. You should therefore
back up OS server PCs or OS client PCs to an image. You can find information on this in the
section "Backing up data by generating an image file (Page 31)".
24
WinCC Information System
Service Support and Diagnostics (V8.2)
Service Manual, 03/2016, A5E36200111-AA