Emergency regulation
During winter operation, in case of sensor failure, in order to avoid problems
regarding freezing, the chronothermostat activates the relay for 10 minutes every 4
hours and field (16) will display the "---" symbol.
Restoring default parameters
Simply pressing the "R" key will not cause a total reset of the instrument. To do so
and allow the loading of the default values, it is necessary to press the "R" key and
then, within 3 seconds, the " " key. The display will show the writing "dEF".
• ON/OFF regulation
The default regulation type is ON/OFF with deactivation in correspondence with the
setpoint and with differential set to 0.3°C.
During on/off operation mode, the relay of remote actuator follows the following
logic:
heating mode
relay ON
relay OFF
SET-DIFF
Temperature
increasing
• Proportional regulation
During heating mode the proportional regulation can be chosen; in certain types
of systems, this allows to improve the regulation, in order to obtain a constant
temperature.
This regulation activates the ON or OFF relay within a predefined regulation cycle on
the basis of the gap of the temperature measured by the setpoint value.
The necessary parameters for the definition of this mode are:
- the regulation band
- the regulation period
REGULATION TYPE
cooling mode
relay ON
relay OFF
Temperature
increasing
- 56 -
Mithos Chronothermostat User Manual
SET
SET+DIFF