The default regulation is of the On-Off type, with the system switched off at the sets
and with fi xed differential of 0.3 °C [0.5 °F]. The examples set out below are for
winter operation. The summer operation is complementary, meaning that if the
command is activate for one it is deactivate for the other..
In On-Off operation, if the measurement is less than the minimum threshold the
load is always on. In proportional regulation, the regulation is on a 10 minute time
base, with the following specifi cations:
Tmis ≥ Tset + 0.6 °C [1.1 °F]
Tmis = Tset + 0.5 °C [0.9 °F]
Tmis = Tset + 0.4 °C [0.7 °F]
Tmis = Tset + 0.3 °C [0.5 °F]
Tmis = Tset + 0.2 °C [0.4 °F]
Tmis = Tset + 0.1 °C [0.2 °F]
Tmis = Tset
Tmis = Tset - 0.1 °C [0.2 °F]
Tmis = Tset - 0.2 °C [0.4 °F]
Tmis = Tset - 0.3 °C [0.5 °F]
Tmis ≤ Tset - 0.4 °C [0.7 °F]
If there is a change in the operating set, the regulation takes place in ON-OFF mode
until the Tset is reached for the fi rst time, to reach the conditions set more rapidly.
DISPLAY DURING OPERATION
DISPLAY DURING OPERATION
The possible display readings and corresponding operation are set out below..
■ Automatic operation:
weekly clock displaying the hour, minutes and day of
the week; temperature graph, ambient temperature,
symbol "C" (default) or "F"; symbol
boiler is active) or symbol
is active).
TYPE OF REGULATION
TYPE OF REGULATION
⁄
⁄
⁄
⁄
⁄
⁄
⁄
⁄
⁄
⁄
⁄
(if the
(if the air conditioner
- 52 -
Manual User Evo.din
relè OFF
1 minute ON; 9 minutes OFF
2 minutes ON; 8 minutes OFF
3 minutes ON; 7 minutes OFF
4 minutes ON; 6 minutes OFF
5 minutes ON; 5 minutes OFF
6 minutes ON; 4 minutes OFF
7 minutes ON; 3 minutes OFF
8 minutes ON; 2 minutes OFF
9 minutes ON; 1 minute OFF
relè ON