Troubleshooting
Check No.06
Refer to P.130
P4
J3
J6
H9
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn on the power again.
Error displayed
again on remote
controller?
YES
Connector or thermistor
disconnected?
NO
Check No. 06
Check the thermistor resistance
value.
Normal?
YES
Check No. 06
Check the indoor heat exchanger
thermistor resistance value in the
heating mode.
Indoor heat
exchanger thermistor
functioning?
YES
:
Radiation fin thermistor
:
Discharge pipe thermistor
:
Outdoor heat exchanger thermistor
:
Outdoor air temperature thermistor
NO
YES
NO
NO
Troubleshooting
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
Radiation fin thermistor
Discharge pipe thermistor
Outdoor heat exchanger
thermistor
Outdoor air thermistor
Replace the following
thermistor.
Indoor heat exchanger
thermistor
Replace the outdoor unit
PCB.
(Replace the indoor unit
PCB.)