Daikin ATXS35EV1B7 Service Manual page 126

Inverter pair e-series
Hide thumbs Also See for ATXS35EV1B7:
Table of Contents

Advertisement

SiBE04-824
Troubleshooting
Check No.06
Refer to P.130
Check No.07
Refer to P.131
Check No.09
Refer to P.132
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn off the power and turn it on
again.
Error again or outdoor
unit fan activated?
NO
Check No. 09
Check the outdoor unit fan
or related.
Functioning
Radiation fin dirty?
Slightly dirty
Check No. 07
Check the installation condition.
: Value for 50 class
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 80˚C (95˚C ) and stops itself
when it drops below 70˚C (80˚C ).
YES
Check No. 06
Check the thermistor resistance
value.
Fin thermistor
Check the radiation fin
temperature.
Thermistor as
specified in its characteristic
chart?
YES
Above 80˚C
(95˚C
YES
Malfunctioning
Too dirty
Troubleshooting
NO
Replace the fin thermistor.
NO
)?
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R8345)
115