WIRING
CHAPTER 3: INSTALLATION
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three
terminals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column
"a" having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single
input/output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The following figure illustrates the
transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.
Where a tilde "~" symbol appears, substitute the slot position of the module.
Figure 3-21: Transducer input/output module wiring
3
The following figure show how to connect RTDs.
3-24
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL