GROUPED ELEMENTS
A time dial multiplier setting allows selection of a multiple of the base curve shape (where the time dial multiplier = 1) with
the curve shape (
CURVE
to the time multiplier (
or base curve values. Setting the multiplier to zero results in an instantaneous response to all current levels above pickup.
Time overcurrent time calculations are made with an internal energy capacity memory variable. When this variable
indicates that the energy capacity has reached 100%, a time overcurrent element operates. If less than 100% energy
capacity is accumulated in this variable and the current falls below the dropout threshold of 97 to 98% of the pickup value,
the variable must be reduced. Two methods of this resetting operation are available: "Instantaneous" and "Timed." The
"Instantaneous" selection is intended for applications with other relays, such as most static relays, which set the energy
capacity directly to zero when the current falls below the reset threshold. The "Timed" selection can be used where the
relay must coordinate with electromechanical relays.
IEEE curves
The IEEE time overcurrent curve shapes conform to industry standards and the IEEE C37.112-1996 curve classifications for
extremely, very, and moderately inverse curves. The IEEE curves are derived from the operate and reset time equations.
where
T = operate time (in seconds)
TDM = Multiplier setting
5
I = input current
I
= Pickup Current setting
pickup
A, B, p = constants defined in the table
T
= reset time in seconds (assuming energy capacity is 100% and RESET is "Timed")
RESET
t
= characteristic constant defined in the table
r
Table 5-29: IEEE inverse time curve constants
IEEE curve shape
IEEE Extremely Inverse
IEEE Very Inverse
IEEE Moderately Inverse
Table 5-30: IEEE curve trip times (in seconds)
Multiplier
Current ( I / I
(TDM)
1.5
IEEE Extremely Inverse
0.5
11.341
1.0
22.682
2.0
45.363
4.0
90.727
6.0
136.090
8.0
181.454
10.0
226.817
IEEE Very Inverse
0.5
8.090
1.0
16.179
2.0
32.358
5-196
) setting. Unlike the electromechanical time dial equivalent, operate times are directly proportional
) setting value. For example, all times for a multiplier of 10 are 10 times the multiplier 1
TD MULTIPLIER
A
B
28.2
0.1217
19.61
0.491
0.0515
0.1140
)
pickup
2.0
3.0
4.0
4.761
1.823
1.001
9.522
3.647
2.002
19.043
7.293
4.003
38.087
14.587
8.007
57.130
21.880
12.010
76.174
29.174
16.014
95.217
36.467
20.017
3.514
1.471
0.899
7.028
2.942
1.798
14.055
5.885
3.597
p
t
r
2.0000
29.1
2.0000
21.6
0.02000
4.85
5.0
6.0
7.0
0.648
0.464
0.355
1.297
0.927
0.709
2.593
1.855
1.418
5.187
3.710
2.837
7.780
5.564
4.255
10.374
7.419
5.674
12.967
9.274
7.092
0.654
0.526
0.450
1.308
1.051
0.900
2.616
2.103
1.799
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Eq. 5-8
8.0
9.0
10.0
0.285
0.237
0.203
0.569
0.474
0.407
1.139
0.948
0.813
2.277
1.897
1.626
3.416
2.845
2.439
4.555
3.794
3.252
5.693
4.742
4.065
0.401
0.368
0.345
0.802
0.736
0.689
1.605
1.472
1.378

Advertisement

Table of Contents
loading

Table of Contents