CHAPTER 5: SETTINGS
The disturbance detector responds to the change in currents of twice the current cut-off level. The default cut-off threshold
is 0.02 pu; thus by default the disturbance detector responds to a change of 0.04 pu. The metering sensitivity setting
(
PRODUCT SETUP  DISPLAY PROPERTIES  CURRENT CUT-OFF LEVEL
accordingly.
5.5.3.4 Example for use of sources
An example of the use of sources is shown in the following figure. A relay can have the following hardware configuration:
This configuration can be used on a two-winding transformer, with one winding connected into a breaker-and-a-half
system. The following figure shows the arrangement of sources used to provide the functions required in this application,
and the CT/VT inputs that are used to provide the data.
Y LV
SRC 1
Phase CT
M1
Ground CT
M1
Phase VT
M5
Aux VT
None
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-58: Example of use of sources
D HV
AUX
SRC 2
SRC 3
F1+F5
None
None
None
None
None
None
U1
) controls the sensitivity of the disturbance detector
SYSTEM SETUP
5
5-133