CHAPTER 5: SETTINGS
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows
setting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after
time-out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile
memory. Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word
(user setting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input
being out of range.
A selector switch runs every two power cycles.
— This setting defines the upper position of the selector. When stepping up through available
SELECTOR 1 FULL RANGE
positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-bit control
word for programming the selector to a desired position, the change would take place only if the control word is within the
range of 1 to the
SELECTOR FULL RANGE
FlexLogic operand for three seconds.
SELECTOR ALARM
— This setting defines the time-out period for the selector. This value is used by the relay in the
SELECTOR 1 TIME-OUT
following two ways. When the
of the control input after which the pre-selected position is automatically applied. When the
"Acknowledge," the setting specifies the period of time for the acknowledging input to appear. The timer is re-started by
any activity of the control input. The acknowledging input must come before the
otherwise, the change does not take place and an alarm is set.
F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
SELECTOR 1 FULL
RANGE: 7
SELECTOR 1 TIME-OUT:
5.0 s
SELECTOR 1 STEP-UP:
Off
SELECTOR 1 STEP-UP
MODE: Time-out
SELECTOR 1 ACK:
Off
SELECTOR 1 3BIT A0:
Off
SELECTOR 1 3BIT A1:
Off
SELECTOR 1 3BIT A2:
Off
SELECTOR 1 3BIT
MODE: Time-out
SELECTOR 1 3BIT ACK:
Off
SELECTOR 1 POWER-UP
MODE: Restore
SELECTOR 1 TARGETS:
Self-reset
SELECTOR 1 EVENTS:
Disabled
. If the control word is outside the range, an alarm is established by setting the
is "Time-out," the setting specifies the required period of inactivity
SELECTOR STEP-UP MODE
Range: 1 to 7 in steps of 1
Range: 3.0 to 60.0 s in steps of 0.1
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
Range: Restore, Synchronize, Sync/Restore
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SELECTOR STEP-UP MODE
timer expires;
SELECTOR 1 TIME-OUT
CONTROL ELEMENTS
5
is
5-255