Air Filter Check Or Substitution - Liebert CR020 User Manual

Crv series
Table of Contents

Advertisement

General
Filters
Blowers
Electrics/electronics
Steam generating
humidifier
Cooling water circuit
(W and C units)
Refrigerating circuit
Air cooled
condenser/dry cooler
(if applicable)
Water/glycol pump
(if applicable)

10.4 Air Filter Check Or Substitution

Every month it's important to check the state of air filter to maintain a good efficiency of air distribution throw the
evaporator coil.
First switch off the CRV, then open the rear panel with the key, access to the fan panel rotating the three locks with
the black key. Wait until fans are stopped (when you open the first lock, you also open a security switch that cut the
current, see Figure 10-1).
Table 10-1 Maintenance schedule
Components
Check unit display for clogged-filter warning
Check for irregular noise from unit fans
Check for irregular noise from compressor
Check for irregular noise from remote condenser fan/s (if
applicable)
Check state of filters
Replace air filter whether necessary
Filter switch functionality check
Verify impellers move freely
Check bearings
Check motor mounts for tightness
Check fan safety switch
Check condition of contactors
Check electrical connections
Check operation of controller
Check unit operation sequence
Check cylinder & pan
Check steam hoses conditions
Verify filling solenoid valve proper operation
Circuit leakage/general condition check
Check water(-glycol) inlet temperature
Check water regulating valve operation
Check in/out water(-glycol)  t
Check mixture glycol level (if applicable)
Check compressor noise/vibrations
Check oil level through compressor sight glass
Adjust/tighten compressor/functional elements
Check sight glass for problem detection
Check starting/running amps
Check refrigerating circuit main pressures
Check compressor suction superheat
Check discharge temperature
Check sub cooling
Check fan/s bearings
Check fan/s motor mounts for tightness
Check coil condition
Check pipelines supports
Check fan/s speed controller operation
See relevant manual
Liebert.CRV Series Air Conditioner User Manual
Chapter 10 Maintenance & Spare Parts
Maintenance period
Monthly
quarterly biannual
×
×
×
×
41
annual
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cr035Cr040

Table of Contents