Appendix 2 Technical Data Tables
CR020RW
CR035RW
Note*:
The recommended oil is EMKARATE RL 32-3MA
Note: The air conditioner is supplied complete with refrigerant and oil.
The detailed sound data of the Liebert.CRV are listed in Table 8.
Airflow
Fan speed
(%)
SCFM
100
2454
75
2166
55
1780
100
3260
75
2708
55
2048
100
3325
75
2708
55
1972
Note: PWL is sound power level; SPL is sound pressure level
Table 7 Refrigerant and oil charge for water cooled models (W type)
Model
Table 8 Sound data of Liebert.CRV
3
m
/h
Level
31.5
4170
PWL
73.8
69.4
3680
PWL
71.2
66.8
3025
PWL
67.6
63.2
5540
PWL
76
76.2
4600
PWL
71.3
71.5
3480
PWL
66.3
66.5
5650
PWL
86.4
78.1
4600
PWL
80.8
72.5
3350
PWL
75.1
66.8
Liebert.CRV Series Air Conditioner User Manual
R410A refrigerant charge (kg)
6.5
11
Octave band frequency(Hz)
63
125
250
500
CR020 air cooled models
71
77.3
75.9
68.4
74.7
73.3
64.8
71.1
69.7
CR035 air cooled models
80.5
82.7
77.3
75.8
78
72.6
70.8
73
67.6
CR040 water cooled models
82.4
84.6
79.2
76.8
79
73.6
71.1
73.3
67.9
Initial oil charge* (kg)
1000
2000
4000
8000
74.2
73.5
68.2
59.2
71.6
70.9
65.6
56.6
68
67.3
62
53
73.1
74.5
69
61.9
68.4
69.8
64.3
57.2
63.4
64.8
59.3
52.2
75
76.4
70.9
63.8
69.4
70.8
65.3
58.2
63.7
65.1
59.6
52.5
1.68
3.08
Unit SPL
Sound
suction
level
(2m from
(dBA)
front, dBA )
79.6
69.2
77
66.9
73.4
63.9
80.9
70.0
76.2
65.7
71.2
61.9
82.8
71.6
77.2
66.0
71.5
60.3