Connection Of Pv Modules - Delta SI 5000 Operation And Installation Manual

Solar inverter
Hide thumbs Also See for SI 5000:
Table of Contents

Advertisement

Available languages

Available languages

The solar inverter must be earthed via the AC connector's PE conductor. To do this, connect the PE
conductor to the designated terminal. If you wish to integrate more than one inverter into the instal-
lation, please proceed as illustrated in the drawings in the appendix.
Please note the cable length and the cable cross-section, due to the risk of undesirable temperature
rise and power losses.
Please note the cable length and the cable cross-section, due to the risk of undesirable temperature
rise and power losses.
6.7
Connection of PV modules
Before the photovoltaic system is connected, the polarity of the PV voltage at the Tyco connectors
must be checked to ensure that it is correct. The connectors are colour coded red (+) and blue (-).
The connection of the PV module is implemented using a Tyco Solarlok connector, where the minus
pole is located on the connector upper row and the positive pole on the connector lower row.
The connectors are coded to prevent you from accidentally plugging them into the wrong terminal.
Please ensure the following at all times:
• that there is never any risk of anyone coming into contact with the solar inverter connection
terminals, due to the risk of dangerous voltages across them.
• that under no circumstances the PV modules are disconnected from the solar inverter under
load. If a disconnection should be necessary, first switch the network off so that the solar inver-
ter cannot absorb any further power. Next, open the upstream DC disconnect switch.
The solar inverter is equipped with the connector connection system from the company Tyco. The
maximum input voltage of the solar inverter is 540 V. The maximum current load of each individual
Tyco connector is 25 A. This is particularly important for the maximum current of 36.6 A. The input
current may have to be distributed across several Tyco input connectors.
The solar inverter has an insulation and grounding monitoring on the DC side. The options can be
configured in the Setup menu "6. S -> Solar ISO / GND" (see page 51, section 7.3.7).
The insulation monitoring has two modes:
• ISO-ON-Error (the solar inverter is disconnected from the mains in the event of an insulation
fault)
• ISO-ON-Warning (the solar inverter indicates the fault but is not disconnected from the mains).
The solar inverters are factory-set to ISO-ON-Warning mode on delivery.
The grounding monitoring has two modes:
• PV+ grounding (grounding monitoring of the positive pole of the PV generator)
• PV- grounding (grounding monitoring of the negative pole of the PV generator).
In these modes the solar inverter remains in feed-in operation and will not be disconnected from
the mains in case of a fault. The error message "PV+ grounding fault" or "PV- grounding fault" will
appear on the display.
If you need to connect the positive or negative pole of the PV system to meet requirements set
out by the module manufacturer, you can do this. Earth continuity must be implemented close to
the inverter. We suggest using Deltas grounding kit "Grounding Set A Solar" (EOE 99000115). The
grounding connection is monitored and should be configured in the Setup menu (see above).
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents