Concrete curing function

When pipes of floor heating are installed, operation for reinforcing concrete curing is applied . (Period of operation: 20 days)
Entering procedure
1 . After turning off the DIP switch K3 (3rd switch of SW03) of control kit (Default ON), turn off and turn on the control kit . The
operation for concrete curing starts automatically . (If blackout occurs and communictation restarts later, operation will
continue . )
2 . Temperature of discharge water is controlled as time goes on like below .
Temp.
60
50
40
30
20
10
0
1
2
3
4
Classification
Initial Heating
Time
96
Temperature
30
3 . Remaining days are displayed on the wired remote controller during operation but key operation is unavailable .
Remaining days
are displayed .
❋ ❋ If an error is displayed, concrete curing function does not work .
42
EHS MONO Kit-EU_IM_05388A-00_EN.indd 42
5
6
7
8
9
10
11
Step raise
48
24
24
55
30
40
12 13
14
15
16 17
18
Heating
24
168
24
50
55
50
Day
19
20
Total
Step down
(Hour)
24
48
480
40
30
-
2015-03-18 오전 11:53:55